10.4.4 CommsMemAlloc
Replaces PakBusNodes. Controls the amount of memory allocated for PakBus routing and
communications in general. Increase the value of this setting if you require more memory
dedicated to communications. Increase this value if the data logger will be used for routing a
large number of PakBus nodes (>50). Increase this value if your data logger is dropping
connections during short periods of high TCP/IP traffic. This setting will effect the values
reported in
.
10.4.5 ConfigCom
x
Specifies the configuration for a data logger control port as it relates to serial communications. It
is significant only when the associated port baud rate setting is set to something other than
Disabled. This setting denotes the physical layer properties used for communications. It does not
indicate the port's current configuration as it relates to standard or inverted logic. Options
include:
l
RS-232: Configures the port as RS-232 with standard voltage levels.
l
TTL: The port is configured to use TTL, 0 to 5V voltage levels. By default, the port will use
inverted logic levels. Use
SerialOpen()
to configure this port for standard TTL logic
levels.
l
LVTTL: The port is configured to use Low Voltage TTL (LVTTL), 0 to 3.3V voltage levels. By
default, the port will use inverted logic levels. Use
SerialOpen()
to configure this port
for standard TTL logic levels.
l
RS-485 Half-Duplex PakBus: The port is configured as RS-485 half-duplex (two wire) and
uses the PakBus/MDROP protocol. This allows reliable PakBus peer-to-peer networking of
multiple devices including the MD485 and NL100 using the RS-485 interface.
l
RS-485 Half-Duplex Transparent: The port is configured as RS-485 half-duplex (two wire).
This setting is most commonly used when communicating with other non-PakBus RS-485
devices. Use this setting when communicating with devices such as Modbus RTUs or third-
party serial sensors with RS-485 interfaces.
l
RS-485 Full Duplex Transparent: The port is configured as RS-485 full-duplex (four wire). In
this configuration, four adjacent control ports will be required.
10.4.6 CSIO
x
netEnable
Controls whether the CS I/O IP #1 or #2 TCP/IP interface should be enabled.
10. Information tables and settings (advanced)