7. Ensure Datalogger Operating System Files (*.obj) is selected in the files of type list, select
the new OS .obj file, and click Open to update the OS on the data logger.
Note the following precautions when sending as a program:
l
Any peripherals being powered through the SW12 terminals will be turned off until the
program logic turns them on again.
l
Operating systems are very large files. Be cautious of data charges. Sending over a direct
serial or USB connection is recommended, when possible.
8.8 File management via powerup.ini
Another way to upload a program, install a data logger OS, or format a drive is to create a
powerup.ini file. The file is created with a text editor and saved to a memory card or SC115 with
the associated files. Alternatively, the powerup.ini file and associated files can be saved to the
data logger using the data logger support software File Control > Send command. With the
memory card or SC115 connected, or with the powerup.ini file saved in the data logger memory, a
power cycle to the data logger begins the process chosen in the powerup.ini file.
When uploading a program, the following rules determine what data logger program to run:
l
If the Run Now program is changed, then it is the program that runs.
l
If no change is made to the Run Now program, but the Run on Power Up program is
changed, the new Run on Power Up program runs.
l
If neither Run on Power Up nor Run Now programs are changed, the previous Run on
Power Up program runs.
8. CR6 maintenance
123