Section 10. Troubleshooting
514
The CR3000 does not catch all out-of-bounds errors, so take care that all arrays
are sized as needed.
10.5.4.8 Watchdog Errors
Watchdog errors indicate the CR3000 has crashed and reset itself. A few
watchdogs indicate the CR3000 is working as designed and are not a concern.
Following are possible root causes sorted in order of most to least probable:
•
Transient voltage
•
Running the CRBasic program very fast
•
Many PortSet() instructions back-to-back with no delay
•
High-speed serial data on multiple ports with very large data packets or
bursts of data
If any of the previous are not the apparent cause, contact a Campbell Scientific
support engineer for assistance. Causes that require assistance include the
following:
•
Memory corruption. Check for memory failures with M command in
terminal mode
(p. 523).
•
Operating-system problem
•
Hardware problem
Watchdog errors may cause comms disruptions, which can make diagnosis and
remediation difficult. The CR1000KD Keyboard/Display will often work as a
user interface when comms fail. Information on CR3000 crashes may be found
in three places.
•
WatchdogErrors
(p. 593)
field in the Status table
•
Watchdog.txt file on the CPU: drive
(p. 446).
Some time may elapse
between when the error occurred and the Watchdog.txt file is created.
Not all errors cause a file to be created. Any time a watchdog.txt file is
created, please consult with a Campbell Scientific support engineer.
•
Crash information may be posted at the end of the CompileResults
(p.
register in the Status
table.
10.5.4.8.1
Status Table WatchdogErrors
Non-zero indicates the CR3000 has crashed, which can be caused by power or
transient-voltage problems, or an operating-system or hardware problem. If
power or transient problems are ruled out, the CR3000 probably needs an
operating-system update or repair
(p. 5)
by Campbell Scientific.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......