Customers who wish to have Campbell Scientific do the update may do so by RMA and sending
the device in to Campbell Scientific. Customers will pay shipping and handling fees but there will
be no charge on the firmware update service. The RMA firmware update service is valid until
December 31, 2020.

The preferred method for updating the module firmware and data logger operating system is
through a direct connection. Remote updating can be done as well but this method does not
have the verbose feedback during the update process that the directly connected method has.

2. CR300 OS update

The data logger operating system (OS) must be version 08.01 or greater before updating the
cellular module firmware. To update the OS it is assumed that the data logger is already set up in
the LoggerNet Setup screen. If this has not been done, you will need to do so.

1. Open the Connect screen, select the station to update.

2. Click the Connect button and wait for the connection to be established.

3. Select Station Status to check the operating system version.

4. If the OS is less than 08.01 then close Station Status and return to the Connect screen.

a. Click File Control.

b. Click Send.

Cellular Module Firmware Update

2

Содержание CR300 series

Страница 1: ...Application Note Revision 05 2019 Copyright 2019 Campbell Scientific Inc...

Страница 2: ...te 2 3 Using a direct USB connection and Device Configuration Utility 4 4 Remote update using LoggerNet 8 5 CELL210 cellular radio firmware update 11 6 If you don t have direct access to the data logg...

Страница 3: ...ed by the cell provider and are required on specific cellular networks You can see if you are using a PPP authentication username and password in Device Configuration Utility Using a direct USB connec...

Страница 4: ...ack during the update process that the directly connected method has 2 CR300 OS update The data logger operating system OS must be version 08 01 or greater before updating the cellular module firmware...

Страница 5: ...rating system it will have an obj extension e Click Open LoggerNet will send the operating system file to the data logger This will take several minutes to complete You may need to stop the running pr...

Страница 6: ...tart Device Configuration Utility Select the CR300 data logger from the list of devices presented in the Device Type field 5 Select the appropriate Communication Port by clicking on the button It shou...

Страница 7: ...ule firmware see If you don t have direct access to the data logger nor a copy of LoggerNet p 15 9 Scroll to the Cell Diagnostic Info field The current version of the cellular module firmware is liste...

Страница 8: ...the CELL200 and CELL205 should look similar to this CR300 CELL UPDATE Are you sure YES NO CR300 YES Restarting cellular modem please wait Restarting modem in firmware update mode Waiting for modem ini...

Страница 9: ...successful Please wait Firmware update time 00 30 Firmware update time 01 00 Firmware update time 01 30 Firmware update time 02 00 Cellular module version 2 00 101 06 Firmware update successful Cellul...

Страница 10: ...4 Remote update using LoggerNet This is the best method to use if using the Konect PakBus Router service to access the CR3X0 CELL2XX device It is assumed that the data logger is already set up in the...

Страница 11: ...bottom of the screen The current version of the cellular module firmware is listed next to Brio Ver If it is greater than the version listed below you do not need to update the module firmware CELL200...

Страница 12: ...data logger is Restarting cellular modem please wait LoggerNet will disconnect 10 Close the Terminal window then click Cancel in the Connect screen 11 Wait up to 20 minutes for the modem firmware to u...

Страница 13: ...f devices presented in the Device Type field 5 Select the appropriate Communication Port by clicking on the button It should have CR300 listed in the name If not install the appropriate driver by clic...

Страница 14: ...then Cellular Wait until the State field says Network ready 11 Select the Terminal tab 12 Press Enter until the CR300 prompt appears 13 Type in all CAPS CELLULAR RADIO UPDATE or CELLULAR RADIO UPDATE...

Страница 15: ...will use approximately 300 KB of the cellular plan data The process can take from 5 to 15 minutes 15 If the update is successful Radio update finished is displayed on the line before Radio firmware u...

Страница 16: ...Cellular Module Firmware Update 14...

Страница 17: ...rNet Customers using the Konect PakBus Router Service should contact Campbell Scientific support directly and a Support Engineer will help l If you use this option please have your Konect PakBus Route...

Страница 18: ...As specified in our warranty policy you are responsible for all costs associated with returning the warranty repair to Campbell Scientific After updating the data logger and modem we will return it to...

Страница 19: ...033 0 1 56 45 15 20 Email info campbellsci fr Website www campbellsci fr Germany Location Bremen Germany Phone 49 0 421 460974 0 Email info campbellsci de Website www campbellsci de South Africa Locat...

Отзывы: