Section 7. Installation
Table 43.
SDI-12 Commands for Transparent Mode
Command Name
Command Syntax
1
Response
2
Notes
Break
Continuous
spacing for at least
12 milliseconds
None
Address Query
?!
a<CR><LF>
Acknowledge Active
a!
a<CR><LF>
Change Address
aAb!
b<CR><LF>
(support for this command is required only if the sensor
supports software changeable addresses)
Start Concurrent Measurement
aC!
atttnn<CR><LF>
Additional Concurrent
Measurements
aC1!
...
aC9!
atttnn<CR><LF>
Additional Concurrent
Measurements and Request CRC
aCC1!
...
aCC9!
atttnn<CR><LF>
Send Data
aD0!
...
aD9!
a<values><CR><LF>
or
a<values><CRC><CR><LF>
Send Identification
aI!
allccccccccmmmmmmvvvxxx...xx<CR><LF>
. For example,
013CampbellCS1234003STD.03.01
means address = 0, SDI-12 protocol
version number = 1.3, manufacturer is Campbell Scientific, CS1234 is the
sensor model number (fictitious in this example), 003 is the sensor version
number, STD.03.01 indicates the sensor revision number is .01.
Start Measurement
3
aM!
atttn<CR><LF>
Start Measurement and Request CRC
3
aMC!
atttn<CR><LF>
Additional Measurements
3
aM1!
...
aM9!
atttn<CR><LF>
Additional Measurements and
Request CRC
3
aMC1!
...
aMC9!
atttn<CR><LF>
Continuous Measurements
aR0!
...
aR9!
a<values><CR><LF>
(formatted like the
D
commands)
Continuous Measurements and
Request CRC
aRC0!
...
aRC9!
a<values><CRC><CR><LF>
(formatted like the
D
commands)
Start Verification
3
aV!
atttn<CR><LF>
1
If the terminator '
!
' is not present, the command will not be issued. The CRBasic
SDI12Recorder()
instruction, however, will still pick up data
resulting from a previously issued
C!
command.
2
Complete response string can be obtained when using the
SDI12Recorder()
instruction by declaring the
Destination
variable
as String
.
3
This command may result in a service request.
SDI-12 Address Commands
Address and identification commands request metadata about the sensor. Connect
only a single probe when using these commands.
?!
Requests the sensor address. Response is address,
a
.
Syntax:
?!
269
Содержание CR1000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 40: ......
Страница 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Страница 96: ......
Страница 98: ...98 ...
Страница 302: ......
Страница 350: ...Section 8 Operation Figure 91 Pulse Sensor Output Signal Types Figure 92 Switch Closure Pulse Sensor 350 ...
Страница 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Страница 454: ...Section 8 Operation 8 8 1 Data Display Figure 116 Displaying Data with the Keyboard Display 454 ...
Страница 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Страница 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Страница 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Страница 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Страница 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Страница 478: ......
Страница 506: ......
Страница 536: ......
Страница 636: ......
Страница 642: ......
Страница 644: ......
Страница 676: ......
Страница 677: ......