Operation and maintenance instructions
Series PRE proportional pressure regulator
External sensor version
5000056022
Ver. 00
23
12.2.
Configurator
By clicking on the button below the image of the device (
) it is possible to
open
the
configurator.
In order to change the parameters, the device must be setted in "Manual" mode.
The parameters are divided into groups and can only be modified by the user with the necessary
permissions, furthermore, based on the version of the regulator, only some parameters will be
visible.
12.2.1.
User setup
Visible parameters (only for versions with LCD):
•
Led timeout: Set the LCD screen timeout. When this time-out expires, the LED-backlit LCD
display and the backlit function keys are switched off. To switch them on again, just press any
key.
Parameters visible only for versions with wireless connection:
•
SSID: network name to connect.
•
Password: password of network name to connect.
•
IP address: IP address of data destination. This is the IP address of PC or gateway where
UVIX used by device is installed.
•
Host port: port number used to send and receive data with the UVIX component designated
for this task
Parameters visible in all versions:
•
External sensor interface: set the type of external sensor electrical signal: Voltage (0-10V) or
Current (4-20mA)
•
Unit of measurement (regulator): serves to set the unit of measurement of the device, all
pressure values present on the LCD (if present, depends on the code) will be expressed in
this unit of measurement. Possible values are: psi, bar or kPa.
•
Pressure regulation check mode: serves to set the event type, warning or alarm, in case the
regulated pressure doesn’t reach the target value. Refer to the “Pressure regulation check
timeout” parameter
.
•
Pressure regulation check timeout: enables to control the regulated pressure. This control is
similar to the "window" function of the digital output (for more details regarding this
function, refer to paragraph "Digital output"): the regulator checks if the regulated pressure
reaches the pressure target within a certain settable time (Pressure regulation timeout). This
control uses the values "Lower limit window control" and "Upper limit window control" to
determine the tolerance range on the regulated pressure.
•
Pressure regulation timeout: serves to set the timeout value for the pressure regulation
check.
Refer to the “Pressure regulation check timeout” parameter.
•
Lower limit window control: serves to set the lower threshold to define the control window.
Refer to the “Pressure regulation check timeout”
parameter.
•
Upper limit window control: serves to set the upper threshold to define the control window.
Refer to the “Pressure regulation check timeout”
parameter.