16
Fig. 2
(3)
Front plate
(6)
Type label
(7)
Transparent cover
(8)
Fixing bracket
(9)
Opening for withdrawing clip (for opening the housing)
(10) Top-hat rail 35
×
15 mm or 35
×
7.5 mm (EN 50 022)
(11) Terminals
(12) Terminals
(13) Space for notes
ON
Green LED for indicating device standing by
6. Technical data
Measuring input
DC current:
Standard ranges
0…20 mA, 4…20 mA, ± 20 mA
Limit values
0…0.1 to 0…50 mA
also live-zero,
start value > 0 to
≤
50% final
value
– 0.1…0…+ 0.1 to
– 50…0…+ 50 mA
also bipolar asymmetrical
R
i
= 15
Ω
DC voltage:
Standard ranges
0…10 V, 2…10 V, ± 10 V
Limit values
0…0.06 to 0…40,
Ex max. 30 V
also live-zero,
start value > 0 to
≤
50% final
value
– 0.06…0…+ 0.06 to
– 40…0…+ 40 V,
Ex max. – 30…0…+ 30 V
R
i
= 100 k
Ω
ON
SINEAX
TV 808
(11)
(12)
(13) (6)
ON
(9)
(10)
(8)
(7)
(3)
without
function
Span
Zero
Camille Bauer AG
CH-5610 Wohlen
Switzerland
Span
Zero
Overload:
DC current
continuously 2-fold
DC voltage
continuously 2-fold
Measuring output
DC current:
Standard ranges
0…20 mA, 4…20 mA, ± 20 mA
Limit values
0…1 to 0…20 mA
0.2…1 to 4…20 mA
– 1…0…+ 1 to – 20…0…+ 20 mA
Burden voltage:
12 V
External resistance:
R
ext
max. [k
Ω
] =
12 V
I
AN
[mA]
I
AN
= Output circuit full-scale value
DC voltage:
Standard ranges
0…10 V, 2…10 V, ± 10 V
Limit values
0…1 to 0…10 V
0.2…1 to 2…10 V
– 1…0…+ 1 to – 10…0…+ 10 V
Burden:
≥
2 k
Ω
Current limiter at
R
ext
max.:
Approx. 1.1
×
I
AN
for current output
Voltage limiter at
R
ext
=
∞
:
Approx. 13 V
Residual ripple in
output current:
< 0.5% p.p.
Response time:
< 50 ms
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 1: Nominal voltages and tolerances
Nominal voltage
U
N
Tolerance
Instrument
version
24... 60 V
DC / AC
DC – 15...+ 33%
AC ± 15%
Standard
(Non-Ex)
85...230 V
1
DC / AC
24... 60 V
DC / AC
DC – 15...+ 33%
AC ± 15%
Type of protection
“Intrinsically safe”
[EEx ia] IIC
85...230 V
AC
± 10%
85...110 V
DC
– 15…+ 10%
1
For power supples > 125 V, the auxiliary circuit should include an
external fuse with a rating
≤
20 A DC.
Power input:
≤
1.2 W resp.
≤
3 VA
Accuracy data
(acc. to DIN/IEC 770)
Basic accuracy:
Limit error
≤
± 0.2%
Including linearity and reproduci-
bility errors