8.5
Installation of Wall-mounted Configurations
Wall-mounted configurations are designed with a wall-flange, allowing airtight installation in a
technical area with filter access from the room.
Wall-mounted configurations can be installed module-by-module or as a completed tower.
PLEASE NOTE:
Access to both sides of the wall is required for the installation.
Precautions :
Wall-mounted configurations are typically front-heavy. They may be unstable
and prone to tipping over under lateral forces during manipulation / transport!
Consult the project drawing for dimensions, overall weight and position
of the center of gravity before manipulating the tower!
The center of gravity will usually remain within the perimeter
of the support legs. Once installed, the wall flange and it's
attachment points have no weight bearing function!
Their only purpose is to provide a sealing surface between
cleanroom and technical area.
Adequate anchor- & gasket solutions will depend on the
wall technology and are to be defined with the installation
contractor.
For both installation as a tower or module-by-module, the
following priorities should be observed :
1.
Alignment and Airtight assembly of modules (safety critical)
2.
Solid attachment to the ground
3.
Attachment to the wall, including appropriate sealing measures