
Calix ODC-80 Installation Guide
83
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Low voltage disconnect alarm
Alarm output
When the alarm occurs, the following message displays:
TID-000 01-09-10 14-15-00
** 001 REPT ALM ENV
"N2-1:MJ,LVD,NSA,9-10,14-15-00,NEND;"
Clearing output
You will see this message once the alarm has been cleared from the system.
TID-000 01-09-10 14-15-00
A 001 REPT EVT ENV
"N2-1:LVD,CL,9-10,14-15-00;"
Description
Severity
The low voltage disconnect (LVD) alarm indicates that the outdoor
cabinet battery voltage has reached -42 VDC and the cabinet will be
shut down soon.
The low voltage disconnect will be activated when the battery voltage
in the cabinet reaches -44 VDC. Once the low voltage disconnect has
been activated the Calix C7 equipment will shut down and customer
will be out of service.
Major
Содержание ODC-10
Страница 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 Chapter Before You Begin Installing the ODC 80...
Страница 8: ......
Страница 23: ...2 Chapter Placing the ODC 80 on a Pad...
Страница 24: ......
Страница 30: ......
Страница 31: ...3 Chapter Installing Power Subscriber Cables and Equipment...
Страница 32: ......
Страница 74: ......
Страница 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80...
Страница 76: ......
Страница 80: ......
Страница 92: ......
Страница 103: ...5 Chapter Reference...
Страница 104: ......
Страница 106: ......