3.10 Clock and Lock Configurations
The MX Series may optionally be equipped for clock and lock mode of operation. This mode is a
special form of Master/Auxiliary, which requires each chassis to have its controller. As such, i
possible to create 2, 3, 6 or 9 phase power systems using 2 to 3 MX chassis. For most 2 or 3
phase configuratio
t is
ns, the normal multi-box mode of operation as described in section 3.8 is
recommended as it provides a single controller (and GPIB/RS232 control interface).
In a clock and lock configuration, each unit has its own front panel controls (as well as individual
GPIB and RS232C interfaces) for operating the supply but the output frequency of the auxiliary
unit(s) (-LKS option) is synchronized (locked) tot he Master MX unit (-LKM).
This mode of operation requires that one MX has the -LKM (Lock Master) option and one or two
3.10.1 Clock/Lock Configuration Settings
MX units have the -LKS (Lock auxiliary) option.
and -LKS equipped MX's are set at the factory at
Clock and lock configuration. settings for -LKM
th time of shipment and can
changed. T
select the UTILITY2, CONFIGURATION screen
y
determines if the unit is a Master or Auxiliary as
e
not be
o check the configuration settings for an MX,
. In the configuration screen, the CLK/LOC entr
follows:
CONFIGURATION 2
Field
Parameter
Description
CLK/LOC
N/A
Stand alone MX or MX-LKM clock and lock
master.
Frequency mode is set to either INT (internal
= default) or SYNC (external sync).
ON
Auxiliary
MX.
Frequency mode selection is INT (internal =
for stand alone use) or EXT (external for
Clock and Lock mode operation.)
Table 3-13: Clock and Lock Configuration settings
Note that the actual mode of operation of a Clock/Lock MX-LKM auxiliary unit is determined by
the Clock mode set in the PROGRAM2 screen. For clock and lock mode of operation, the
master is set to INT and the Auxiliary to EXT.
66 MX
Series
Содержание MX30-1
Страница 4: ...User Manual Rev AJ California Instruments 4 MX Series ...
Страница 33: ...User Manual Rev AJ California Instruments MX Series 33 ilter option schematic Figure 2 12 MX output f ...
Страница 34: ...User Manual Rev AJ California Instruments Figure 2 13 MX45 Output Noise 10 KHz 1 MHz 34 MX Series ...
Страница 50: ...User Manual Rev AJ California Instruments Figure 3 11 MX135 or MX135 MB Output Wiring Rear view 50 MX Series ...
Страница 147: ...User Manual Rev AJ California Instruments Output Status Available on top assembly 7003 427 only MX Series 147 ...
Страница 148: ...User Manual Rev AJ 148 California Instruments MX Series Figure 5 2 MX Series Detailed Block Diagram ...
Страница 149: ...User Manual Rev AJ MX Series California Instruments 149 Figure 5 3 Power Module Detailed Block Diagram ...
Страница 195: ...User Manual Rev AJ California Instruments Figure 9 4 Voltage Modulation MX Series 195 ...