Function
Scald Protection Three-Way Thermostatic mixing valves are used in
applications where the user must be protected from the danger of
scalding caused by hot water.
The Caleffi 5213 series provides water at a safe and usable
temperature in situations where the control of the temperature
of the water discharging from a terminal fitting is of the utmost
importance, i.e. within hospitals, schools, nursing homes, etc.
The valve is designed to prevent the flow of water discharging from
the mixed water outlet in the event of the failure of hot or cold supply.
The Caleffi 5213 series is a high performance thermostatic mixing
valve and is ASSE 1070 listed.
The valve is complete with check valve at both hot and cold inlets.
Product range
5213 series scald protection three-way thermostatic mixing valve.
Union thread NPT male connections, sizes 1/2”, 3/4”,1”;
Union sweat connection, size 1/2”, 3/4”, 1”.
Scald Protection 3-Way Thermostatic Mixing Valve
Installation, commissioning and servicing instructions
Technical specifications
Materials:
- valve body and regulating spindle:
low-lead brass (<0.25% Lead content)
- internal shutter:
PPO
- sealing elements:
EPDM
- cover:
ABS
Temperature adjustment range:
85–120°F (29–49°C)
Temperature set:
must be commissioned on site to achieve desired temperature
Temperature control:
±3°F (±2°C)
Cold inlet temperature:
Minimum 39°F (4°C); Maximum 85°F (29°C)
Hot inlet temperature:
Minimum 120°F (49°C); Maximum 185°F (85°C)
Maximum working pressure:
Static 150 psi (10 bar); Dynamic 70 psi (5 bar)
Minimum working pressure (dynamic):
1.5 psi (0.1 bar)
Maximum unbalanced dynamic supply (hot/cold or cold/hot):
6:1
Minimum temperature differential between hot water inlet
and mixed water outlet to ensure thermal shutoff function:
18°F (10°C)
Minimum temperature differential between mixed water outlet
and cold water inlet to ensure stable operation:
9°F (5°C)
Minimum flow rate for stable operation:
0.5 gpm (2 l/min)
Certifications: 1. ASSE 1070/CSA B125.3-2012, certified by ICC-ES, file PMG-1358.
2. NSF/ANSI 372-2011, Drinking Water Systems Components-Lead
Content Reduction of Lead in Drinking Water, California Health and
Safety Code 116875 S.3874, Reduction of Lead in Drinking Water
Act, certified by ICC-ES, file PMG-1360.
1
© Copyright 2016 Caleffi
5213 Series
38531.06
www.caleffi.com