Caleffi solar SOLARINCAL-T 262 Series Скачать руководство пользователя страница 4

Safety 

·  The group with thermostatic mixing valve must be installed by a qualified technician in accordance with national regulations and/or

local requirements.

·  If the group with mixing valve is not installed, commissioned and maintained correctly in accordance with the instructions in this

manual, it may not work properly and may put the user in danger.

·  Make sure that all connection fittings are watertight.

·  When realising water connections, make sure that the pipework connected to the group with mixing valve is not subjected to excessive mechanical

stress. Over time this may result in breakages, with consequent water leaks which could harm people and/or damage property.

·  Water temperatures higher than 50°C may cause severe burns. When installing, commissioning and maintaining the group with thermostatic mixing

valve, take the necessary precautions so that these temperatures will not be hazardous for people.

  

·  In the case of particularly aggressive water, water treatment must be provided upstream of the inlet to the group with thermostatic mixing valve,

according to current specifications. If they are not provided the valve may be damaged and may not work properly.

  

·  The  coupling  of  the  kit  with  mixing  valve  and  the  boiler  must  be  made  taking  in  consideration  the  operational  characteristics  of  both  units.

An uncorrect choice could compromise the operation of the boiler and/or system.

Troubleshooting 

In  normal  operating  conditions,  the  unit  provides  high  performance.  However,  in  special  circumstances  when  our  maintenance  schedule  is  not
observed, the following problems may arise:

Problem

Hot water supplied to cold
water taps

Mixed water temperature
fluctuations

Incorrect flow rate at the valve
outlet

No flow at the valve outlet

Anti-scald function not
available when the valve is
tested

Cause

a)  Check valves at the inlets not operating correctly

and watertightness not guaranteed

a)  Incorrect inlet water temperatures
b)  Inlet water supply failure 
c)  Uncorrect commissioning

a)  Insufficient water supply
b)  Inlet water temperature/pressure fluctuations
c)  Adverse conditions due to other water draw off

points in the system

a)  In-line strainers obstructed
b)  Insufficient supply pressure
c)  Dirt obstructing water flow through the valve

a)  Installation not compliant with recommendations
b)  Minimum temperature difference not reached
e)  Inner mechanism obstructed by dirt

Solution

•   Replace damaged check valves

•   Restore inlet conditions within kit

specification range

•   Stabilise supply conditions at the inlet

•   Clean strainers
•   Restore supply conditions
•   Remove dirt/scale from the valve

•   Follow installation instructions
•   Increase hot water temperature
•   Remove dirt/scale from the valve