CALECTRO UniGuard Superflow UG-3-O-MB-R Скачать руководство пользователя страница 5

Modbuskonfigurering.

7

Modbus configuration.

MODBUS-INSTÄLLNINGAR

(DIP-switch: 0 = OFF / 1 = ON)

Modbus ID

DIP-switch 
1,2,3,4,5 och 6

1

000000

2

100000

3

010000

4

110000

5

001000

6

101000

7

011000

8

111000

9

000100

10

100100

11

010100

12

110100

13

001100

14

101100

15

011100

16

111100

17

000010

18

100010

19

010010

20

110010

Modbus Parity

DIP-switch 7 och 8

None (2 stop bits)

00

None (1 stop bit)

11

Even (1 stop bit)

10

Odd (1 stop bit)

01

Modbus Baud rate

DIP-switch 9 och 10

9600

00

19200

10

38400

01

57600

11

TERMINERING

Jumper 1 ON

120 Ohm Termination

DISCRETE INPUTS 

Discrete 
Inputs(1x)

Function

Value range

Read/
Write

1x0001

Detector mounted

0 or 1

R

1x0002

Service alarm

0 or 1

R

1x0003

Smoke alarm

0 or 1

R

1x0004

Relay status

0 or 1

R

HOLDING REGISTER

Holding 
reg. (4x)

Function

Value range

Read/
Write

4x0001

Alarm reset

0 or 234

R/W

4x0002

Alarm reset code

234

R

4x0003

Manual activate 
relay

0 or 567

R/W

4x0004

Manual activate 
relay code

567

R

Содержание UniGuard Superflow UG-3-O-MB-R

Страница 1: ...e air flow direction arrows see the Uniguard foot s shape or on the housing top corresponding to the direction of the air flow in the duct The Uniguard can be installed on any side of the duct N B Rectangular ducts In order to gain maximum air sampling coverage install the Uniguard on the shortest side of a rectangular duct We recommend that the Uniguard is mounted at an equal distance from heatin...

Страница 2: ...uard Lås fast röret med stoppskruven Kapa EJ denna ände DO NOT cut this end Ändplugg End plugg Drill a hole in the duct Without mounting bracket ø 38 mm With UG bracket and or venturi pipe with booster fan ø 51 mm see para 11 Measure the diameter of the duct Shorten the pipe if necessary The pipe should penetrate at least 90 of the width of the duct NOTE See para 9 Insert the end plug Mount the bl...

Страница 3: ...the duct Flödesindikator och fläktrör Flödesindikator Flow indicator The Uniguard is supplied with an indicator a plastic tongue which when the detector is correctly installed is bent outwards due to the airflow NOTE If the indicator does not move you should consider a new mounting positioning of the Uniguard or install a booster fan venturi pipe With installation of a booster fan venturi pipe a m...

Страница 4: ...g demonteras de förmonterade genom att först trycka igenom ena sidan och därefter den andra 1 2 1 2 Remove the cover over the printed circuit board by opening the snap locking Enter the cable through one of the Klikseal glands When using another type of cable gland dismount the ones already installed by first pressing one side through the hole and then the other one 1 2 Electrical installation Snä...

Страница 5: ... None 1 stop bit 11 Even 1 stop bit 10 Odd 1 stop bit 01 Modbus Baud rate DIP switch 9 och 10 9600 00 19200 10 38400 01 57600 11 TERMINERING Jumper 1 ON 120 Ohm Termination DISCRETE INPUTS Discrete Inputs 1x Function Value range Read Write 1x0001 Detector mounted 0 or 1 R 1x0002 Service alarm 0 or 1 R 1x0003 Smoke alarm 0 or 1 R 1x0004 Relay status 0 or 1 R HOLDING REGISTER Holding reg 4x Function...

Страница 6: ...m NOTE Håltagning Ø 51 mm OBS Kanalbredd större än 0 6 m Venturiröret skall gå igenom hela kanalen Diameter of the duct bigger than 0 6 m The venturi pipe should penetrate the whole duct Håltagning Ø 38 mm Drill a hole Ø 38 mm Håltagning Ø 38 mm Drill a hole Ø 38 mm Max kanalbredd 0 6 m Använd venturirör 0 6 m Kapa eventuellt till rätt längd Max diameter of the duct 0 6 m Use the venturi pipe 0 6 ...

Страница 7: ...eringsbeslaget levereras plant The mounting bracket is supplied flat Monteringsbeslaget är lätt att böja forma så att det passar runda eller plana kanaler The mounting bracket can easily be bent or shaped to fit circular or rectangular duct Håltagning Ø 51 mm Drill a hole Ø 51 mm Fäst beslagets ben på kanalen Fix the bracket on to the duct Rund kanal Circular duct Gummi tätning Rubber gasket Isole...

Страница 8: ...ning Rökdetektorn larmar utan rökpåverkan Rökdetektorn är trasig smutsig eller placerad så att kondens bildas Se punkt 10 Detektorinsatsen behöver bytas ut Trouble shooting The smoke detector indicates alarm without smoke Smoke detector is faulty contaminated with dirt or condensation See para 10 The detector needs to be replaced Enligt WEEE Waste of Electrical and Electronic Equipment direktiv sk...

Отзывы: