Modbuskonfigurering.
7
Modbus configuration.
MODBUS-INSTÄLLNINGAR
(DIP-switch: 0 = OFF / 1 = ON)
Modbus ID
DIP-switch
1,2,3,4,5 och 6
1
000000
2
100000
3
010000
4
110000
5
001000
6
101000
7
011000
8
111000
9
000100
10
100100
11
010100
12
110100
13
001100
14
101100
15
011100
16
111100
17
000010
18
100010
19
010010
20
110010
Modbus Parity
DIP-switch 7 och 8
None (2 stop bits)
00
None (1 stop bit)
11
Even (1 stop bit)
10
Odd (1 stop bit)
01
Modbus Baud rate
DIP-switch 9 och 10
9600
00
19200
10
38400
01
57600
11
TERMINERING
Jumper 1 ON
120 Ohm Termination
DISCRETE INPUTS
Discrete
Inputs(1x)
Function
Value range
Read/
Write
1x0001
Detector mounted
0 or 1
R
1x0002
Service alarm
0 or 1
R
1x0003
Smoke alarm
0 or 1
R
1x0004
Relay status
0 or 1
R
HOLDING REGISTER
Holding
reg. (4x)
Function
Value range
Read/
Write
4x0001
Alarm reset
0 or 234
R/W
4x0002
Alarm reset code
234
R
4x0003
Manual activate
relay
0 or 567
R/W
4x0004
Manual activate
relay code
567
R