Temperature / Ohm table

Sensor type

Temperature Ohm

Pt1000

0°C 

20°C 

40°C

1000 

1078 

1156

Pt 100

0°C 

20°C 

40°C

100 

107.8 

115.6

Ni1000

0°C 

20°C 

40°C

1000 

1090.7 

1185.7

NTC 

(Calectro type 

22/33/44/55/99)

0°C 

20°C 

40°C

37942 

14871 

6539

PTC 

(Calectro type 95)

0°C 

20°C 

40°C

1631 

1915 

2226

13. FIGURES

FIG. 1

45

1  2  3  4      5  6  7  8

9 10 11 12     13 14 15 16

60 86

52,5/3 mod.

54

29

19

11

59

FIG. 2 (CFA-24V)

The relay outputs are shown in alarm/

no power on condition. Max 5A, 250V.

24V AC

24V AC

Relay 1

Relay 1

Relay 1

Relay 2

Relay 2

Relay 2

1 2

L N

3 4

5 6 7 8

9 10 11 12 13 14 15 16

GND

Temp. sensor

Temp. sensor

Digital in

Analogue out

Analogue in

Not used

Not used

RC/

DUC

FIG. 3 (CFA-230V)

The relay outputs are shown in alarm/

no power on condition. Max 5A, 250V.

230V AC

230V AC

Relay 1

Relay 1

Relay 1

Relay 2

Relay 2

Relay 2

1 2

L N

3 4

5 6 7 8

9 10 11 12 13 14 15 16

GND

Temp. sensor

Temp. sensor

Digital in

Analogue out

Analogue in

Not used

Not used

RC/

DUC

14.  CONNECTION EXAMPLE FOR CFA-24V AND 

CFA-230V

The relays are shown in alarm/ no power on 

condition.

1 2

24V AC

The relays are shown in a de-energised state

3 4

5 6 7 8

Relay 1

Relay 2

1 2

230V AC

The relays are shown in a de-energised state

3 4

5 6 7 8

Relay 1

Relay 2

Содержание CFA-24V

Страница 1: ...r temperature in the heating coil is normally regulated by another regulator DUC with the controlsignal 0 10or10 0V connectedviaCFAtothe control valve If the water temperature in the coil drops without any response from the regulator DUC CFA starts regulating the control valve When the water temperature in the coil drops below the pre set alarm temperature both relay outlets fall normally activate...

Страница 2: ... and PTC sensors in the ETF series Pt1000 is a factory set sensor 2 Press the Menu button to enter the menu system 3 The current type of temperature sensor is shown 4 Press Menu Enter to change the tempera ture sensor type 5 The current sensor type begins to blink and you can now use the arrow buttons to select another sensor type Press Enter to confirm your selection 6 Use the arrow keys and conf...

Страница 3: ...2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analogue in Not used Not used RC DUC FIG 3 CFA 230V The relay outputs are shown in alarm no power on condition Max 5A 250V 230V AC 230V AC Relay 1 Relay 1 Relay 1 Relay 2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analo...

Страница 4: ...gh Exit Menu Enter Select the desired output signal 0 10V or 10 0V Confirm with Enter Enter Ni 1000 C C Adj Menu Enter Enter Menu C DI Menu C DI Press Menu to access the Menu System Navigate between the submenus using the arrow keys and select sub menu with Menu Enter Select the type of temperature sensor Navigate between the different types and confirm with Enter If necessary the temperature meas...

Отзывы: