CALECTRO CFA-24V Скачать руководство пользователя страница 2

The setpoint for warming function (night mode), 

which is shown in the display’s top right-hand corner, 

now begins to blink. Use ▲ to ▼ change to desired 

value and press Enter to confirm ( ). Ready!

Enter

°

C

DI

 





These settings can also be changed during an alarm.

9.  RESETTING THE ALARM

When the alarm triggers, the relays remain in alarm 

mode until the reset button is pressed.
Freeze alarm in daytime mode

Reset

Alarm

°

C

1 2

DI

 

 

 

Freeze alarm in night mode

Reset

Alarm

°

C

1 2

 



 

If the alarm mode returns to normal temperature 

when the Reset button is pressed, the relays are 

reset and the middle button returns to the Menu  

function.
If the alarm is still triggered after the Reset button is 

pressed, the relays have not been reset and Alarm 

and Reset blink three times. The middle button then 

returns to the Menu function for 20 seconds to allow 

settings to be changed in the menu system before 

returning to Reset.
Reset depressed in alarm mode (daytime mode)

Reset

Alarm

°

C

1 2

DI

 

 

 

Reset depressed in alarm mode (night mode)

Reset

Alarm

°

C

1 2

 



 

6.   BUTTONS AND MENU SYSTEM

▲ = Step up in the menu / increase value - Keep 

the button depressed and the setpoint counts up 

rapidly.

▼ = Step down in the menu / decrease value - 

Keep  the  button  depressed  and  the  setpoint 

counts down rapidly.

 = Is a multifunction button, the current status* 

of which is shown on the display next to the but-

ton.

* Middle button functions:
•  Exit Menu = Exit the menu / Save setting
•  Menu = Enter the menu or select application
•  Enter = Confirm setting 
•  Reset = Resets the relay after an alarm.

Menu

Enter

Reset

Exit

The menu system comprises of the following 

sub-menus:

1.  Selection of temperature sensor
2. Fine-adjustment of the temperature  

measurement

4. Selection of output signal: 0-10 or 10-0V
5. Exit the menu system

7.  SELECTION OF TEMPERATURE 

SENSOR

CFA can be connected to a range of temperature 

sensors: Pt100, Pt1000, Ni1000 plus Calectros 

NTC and PTC sensors in the ETF series. Pt1000 

is a factory set sensor.

2. Press the Menu button ( ) to enter the 

menu system

3. The current type of temperature sensor is 

shown

4. Press Menu-Enter to change the tempera-

ture sensor type

5. The current sensor type begins to blink and 

you can now use the arrow buttons to select 

another sensor type. Press Enter to confirm 

your selection.

6. Use the arrow keys and confirm Exit-Menu 

to exit

8.  SETTING THE ALARM TEMPERATURE 

AND HEAT RETENSION SETPOINT

To change the alarm temperature, press ▲ or 

▼ to the desired value. The alarm temperature, 

which is shown in the top left-hand corner, blinks 

during setting. Press Enter to confirm ( ).

Enter

°

C

DI

 

 



The alarm temperature and warming function  

setpoint can always be adjusted, even during 

alarm mode. See 8.

10.  FINE ADJUSTMENT OF THE 

TEMPERATURE MEASUREMENT

The temperature measurement in CFA can be 

adjusted if necessary. Range: -3°C to +3°C in 

steps of 0.1°C.

1. Press the Menu button ( ) to access the 

menu system

2. Press the arrow key until ‘Adj’ shows on the 

display

3. Press Menu-Enter to adjust
4. The current compensation and temperature 

starts to blink and you can now adjust the 

compensation using the arrow keys. Press 

Enter to confirm your selection ( ).

5. Use the arrow keys and confirm Exit-Menu 

to exit

11.  DISPLAY EXAMPLE

The below example shows CFA in daytime 

mode. The freeze alarm has triggered.

Reset

Alarm

°

C

1 2

DI

 

 

 

Current temperature

Digital inlet 

short circuited = daytime mode

Daytime mode: 4°C

p-band

Both relays have 

been deactivated = 

alarm mode

Alarm temperature

Alarm mode

The below example shows CFA in night mode 

/ warming function. The freeze alarm has trig-

gered.

Reset

Alarm

°

C

1 2

 



 

Current temperature

Night mode/

warming function

Both relays have 

been deactivated = 

alarm mode

Alarm temperature

Alarm mode

12.  ERROR CODES

CFA monitors the temperature sensor so that a 

short circuit or interruption on the sensor circuit 

triggers the alarm and sets the control signal at 

100%.

Er0  Interruption on the sensor input
Er1  Short circuit on the sensor input
Er2  Temperature sensor out of range

Содержание CFA-24V

Страница 1: ...r temperature in the heating coil is normally regulated by another regulator DUC with the controlsignal 0 10or10 0V connectedviaCFAtothe control valve If the water temperature in the coil drops without any response from the regulator DUC CFA starts regulating the control valve When the water temperature in the coil drops below the pre set alarm temperature both relay outlets fall normally activate...

Страница 2: ... and PTC sensors in the ETF series Pt1000 is a factory set sensor 2 Press the Menu button to enter the menu system 3 The current type of temperature sensor is shown 4 Press Menu Enter to change the tempera ture sensor type 5 The current sensor type begins to blink and you can now use the arrow buttons to select another sensor type Press Enter to confirm your selection 6 Use the arrow keys and conf...

Страница 3: ...2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analogue in Not used Not used RC DUC FIG 3 CFA 230V The relay outputs are shown in alarm no power on condition Max 5A 250V 230V AC 230V AC Relay 1 Relay 1 Relay 1 Relay 2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analo...

Страница 4: ...gh Exit Menu Enter Select the desired output signal 0 10V or 10 0V Confirm with Enter Enter Ni 1000 C C Adj Menu Enter Enter Menu C DI Menu C DI Press Menu to access the Menu System Navigate between the submenus using the arrow keys and select sub menu with Menu Enter Select the type of temperature sensor Navigate between the different types and confirm with Enter If necessary the temperature meas...

Отзывы: