2.4
AC Input Power Connection
There is a potential electrical shock hazard when using a PS
without protection. Do not connect PS to AC supply line
without input protection properly assembled.
Connection of this PS to an AC mains should be made by an
electrician or other qualified personnel.
There is a potential shock hazard if the PS chassis (with cover
in place) is not connected to an electrical safety ground via
the safety ground terminal in the AC input connector.
AC Input Wires No Conductor Pretreatment: all kinds of
copper conductors can be clamped without pretreatment
(Solid, Flexible, with ferrule, with/without plastic sleeve). It
is forbidden to solder the conductors. The solder tin yields
and fractures under high pressure. The result is an increased
contact resistance and an excessive temperature rise. In
addition, corrosion caused by pickling or fluxes has been
observed on soldered conductor ends. Notch fractures at the
transition point from the rigid to the flexible conductor area
are also possible.
The PS ON/OFF switch is not the main "disconnect device"
and does not completely disconnect all the circuits from the
AC mains. An appropriately rated "disconnect device" such
as circuit breaker, industrial plug complying with IEC 60309
or with a comparable national standard, etc., shall be
provided in the final installation. The "disconnect device"
shall disconnect all supply lines simultaneously. The
"disconnect device" must be easily accessible.
The connection of this PS to an AC power source should be made by an
electrician or other qualified personnel. The PS shall be connected to the AC source via
protective device (circuit braker, fuses, etc.) rated 20 A max.
WARNING
CAUTION
CAUTION
CAUTION
CAUTION