LEGEND
Fig. 6 page 9
1
Room to ventilate
2
External air inlet
•
The room must be endowed with an external air recycling for a good climate in your ambient.
•
The air inflow from outside to the inner occurs directly, through an opening on the external wall of the room
(see
Fig. 6 page 9
).
•
Bedrooms, garages, and store of flammable materials are excluded.
•
The air inlet should have a total net surface of 80 sqcm
2
: the aforesaid surface is to widen if inside the room
there are other activated appliances (for example: electric ventilators for foul air suction, cooker hoods, other
stoves, etc...) which depress the environment.
•
At switched on appliance it is necessary to check that the pressure fall between the room and the outside
does not exceed 4,0 Pa value: if necessary widen the air inlet (EN 13384).
•
The air inlet must be realized at a height close to the floor with an external grid against birds. In such a way it
cannot be obstructed by any object.
•
In case of installation with sealed-chamber the air inlet is not necessary.
9.9
COMBUSTIBLE AIR INLET FOR SEALED-CHAMBER INSTALLATION
Check
page 36
if the purchased stove has a sealed-chamber. If the stove is endowed with a sealed-chamber
and you want also the whole installation with sealed chamber, please read the following instructions:
•
It is necessary to extract the air for combustion directly from outside.
•
Use a tube with minimum Ø60 mm and maximum 2 meters lenght; to connect see the back of the stove.
•
French standards require installation in double-walled flues (concentric system). The combustion air is drawn
from the cavity.
•
During installation step is necessary to verify the minimum distances required for the combustible air inlet as
(for example) an open door or window causes a vortex which could remove the combustible air necessary
to the stove (see the underlying scheme).
•
On the external wall it is necessary to install a curve at 90° to protect the combustible air inflow from wind
effects: turn the curve inlet downwards, see
Fig. 7 page 10
.
•
Endow the curve with an external shield grid against birds in such a way that it cannot be obstructed by any
object.
Check with your local authorities if exists any restrictive regulation regarding the combustible
air inlet: if present, they must be applied
In some countries and/or regions the installation with sealed-chamber is obligatory: in case
of doubt, please follow the most restrictive regulations.
Fig. 7 - Air inlet for sealed-chamber installation
LEGEND
Fig. 7 page 10
1
≥ 1,5 mt