BWT WRAS Powermag Скачать руководство пользователя страница 1

Powermag

R

R

 

Содержание WRAS Powermag

Страница 1: ...Powermag R R ...

Страница 2: ...Powermag needs to be installed by a professional installer If you require installation please call our sales office on 01494 838107 ...

Страница 3: ...ystem without leaving deposits of scale within the system The Powermag physical water conditioner doesn t introduce sodium into the water therefore the water remains potable The Powermag does not require a separate drain It can be installed direct in line without the aid of a bypass There are no moving parts which means the unit can operate with a limited amount of servicing hysical water conditio...

Страница 4: ...rk that may be required Recommended Installations Powermag units are best installed in one of the following positions Gravity downfeed from a central water tank After a booster pump Directly on the cold mains supply where all outlets are mains fed NB Great care must be taken when installing the Powermag vertically as this may result in damage to the magnetic coil The Powermag control box should be...

Страница 5: ...urrent of magnetic coil in amps Hours Run Total hours of coil operation since installation NOTE Service Warning Lamp will illuminate when service interval has been reached please contact BWT Service when this occurs Activity LED Display Visual display of coil operation LED will run left to right when active and halt when inactive If fault status is initiated alternating LEDs in the strip will illu...

Страница 6: ... filter must be kept clean Isolation switch PCB electronic control 7 8 9 Thermistor Coil LNE Power in connection For interface to BMS and fault monitoring systems Shown in the power OFF state When the power is applied to the control panel the relay will change state i e Terminals 7 8 will be CLOSED Terminals 8 9 will be OPEN Display brightness control Inlet water temperature coil cut out adjustmen...

Страница 7: ...ectifier assembly Secondary DC supply MCB repeatedly trips out Fault on the magnetic coil Test and replace the magnetic coil Panel overheats Poor circulation in the panel Loose connections on high power lines Check clean replace the cooling fan and outlet filter Secure all loose connections and replace wiring where necessary Fault contacts remain closed No power to panel Check mains inlet voltage ...

Страница 8: ...fier assembly PMBHA Fan kit PMFAN3 Fan Filter Pack 5 Filters PMFILPK Fault relay PMREL1 Electronic display PMDB1 Smoothing capacitor PMCAP Thermistor with lead PMTHL EMF diode PMEMF 10A MCB PMCB10 16A MCB PMCB16 Spare parts list Notes For spares orders please contact BWT on Tel 01494 838107 Fax 01494 523833 Email commercial bwt uk co uk ...

Страница 9: ...Power Supply Max water temperature C Power consumption kW Max pressure bar 1 5 3 0 6 0 8 0 12 0 30 0 2 0 2 0 2 0 2 0 2 0 2 230V 50Hz 230V 50Hz 230V 50Hz 230V 50Hz 230V 50Hz 230V 50Hz 25 25 25 25 25 25 0 3 0 3 0 3 0 3 0 3 0 3 16 16 16 16 16 16 Mechanical specification P100 Transformer voltage Mains MCB AC supply MCB DC supply MCB 13 5V 2A 10A 10A 16V P200 P150 16V 6A 6A 20A 20A 16A 16A P250 P300 P4...

Страница 10: ... the date of Installation What services and associated costs are not included Repairs due to breakdown caused by but not limited to Use of the unit for purposes for which it was not designed or intended Incorrect installation e g the failure to follow instructions or advice given by Culligan or it representatives Any defect caused by malicious or wilful action negligence misuse or third part inter...

Страница 11: ......

Страница 12: ...nation Road High Wycombe Buckinghamshire HP12 3SU Tel 01494 838107 Fax 01494 523833 Email commercial bwt uk co uk www bwt uk co uk In the interest of product development we reserve the right to alter specification without prior notice E OE ME0650 ...

Страница 13: ...r supply 230v 50Hz Single phase EMF Emissions Nil Control panel IP55 Construction Material Stainless steel pipework Control Panel Dimensions H X W X D 400 X 300 X 245mm Weight 10Kg Power Consumption 0 3kW Powermag Electromagnetic Scale Inhibitor An electromagnetic physical water conditioner uses the principles of magnetism to inhibit formations of hard crystalline scale within hot and cold water s...

Страница 14: ...of date Please check with BWT UK for final specifications Product Data Sheet GB PM100S Powermag 1 BWT UK Limited BWT House The Gateway Centre Coronation Road High Wycombe Buckinghamshire HP12 3SU Tel 44 0 1494 838100 Fax 44 0 1494 838137 Email enquiries bwt uk co uk www bwt uk co uk Ø 190mm 180mm 110mm Inlet Outlet connection 1 BSP Male 0 5 10 15 20 25 30 0 03 0 09 0 18 0 3 0 45 0 61 Lts Sec Flow ...