EN
35
12.2
Circulation pump specifications
(Must be supplied by the customer; not included in the scope of delivery of the UV unit)
Specification
Q (m³/h) H (bar) P (kW)
Voltage
Type
Rpm
Grundfos CR 10-3A-FJ-A-E_HQQE or
equivalent product
10
2.2
1.1
3x 220-240/380
415YV 50 Hz
Centrifugal, vertical
in-line multi-stage
2840–2870
12.3
Ozone booster specifications
Specification
Material / Nominal Value / Equipment
Model number
0.5
Ozone production method
Corona discharge
High-voltage electrode
Material: Titanium, purity ≥ 99.6%
Dielectric
Quartz tube
Amount of ozone
500 mg/h with a gas flow of 2.5 l/min at
< 20% relative humidity and 25°C
Ozone concentration
> 5 mg/l with gas flow of 1 l/min at < 20% humidity and 25°C
External connections (inlet/outlet) for air/ozone
Material: AISI 304 (1.4301) stainless steel for connecting the PTFE hoses
(8 mm external diameter/6 mm internal diameter)
Minimum length of the electrical lines
600 mm (red/black)
Input voltage
DC 2 V, 1 A
Power consumption
< 12 W
Running time
4 h/day
Cooling system
Internal air cooling, 0.85 m³ per minute
Operating temperature
-10 to +60°C
Storage temperature
-20 to +70°C
Dimensions (L x W x H)
30 mm x 60.5 mm x 79 mm
Product weight
0.55 kg