GasAlertMicro 5 IR
Attach the Gas Cylinder to the Detector
7
Procedure Display
7. When the span is complete, the following
three screens display:
- Calibration successful
- Press
G
to apply a new cal gas
- Press
H
to end span
Repeat steps #4-7 to calibrate the
remaining sensors.
The LCD displays the following options:
Press
C
to set or press
A
to bypass the
calibration due dates.
8. Press
H
or
G
to change the calibration
due date. Press
C
to accept the value
and proceed to the next due date. If a
sensor failed or did not span, the
calibration due date cannot be changed
for that sensor.
The LCD displays the following options:
Press
C
to set or press
A
to bypass the
alarm setpoints.
9. Press
H
or
G
to change the alarm
setpoint. Press
C
to save the value and
proceed to the next setpoint.
Set the remaining setpoints. The
detector beeps twice when all of the
alarm setpoints have been set or
bypassed.
Procedure Display
10. When calibration is complete
, Saving
calibration
displays.
Note
Only use the calibration cap and single
gas calibration cap during the calibration
process.
Attach the Gas Cylinder to the Detector
If an O
3
or ClO
2
sensor is located in the Toxic 2 sensor
position, a single gas calibration cap must be used. For
complete information and procedures, refer to the
GasAlertMicro 5/PID/IR User Manual
.