TROUBLESHOOTING CHARTS

PROBLEM

POSSIBLE CAUSE

SOLUTION

Unit will not turn ON

Defective Power Switch or PCB

Replace defective electrical component

Recovery process is slow

Plugged Filter

Compressor seals are worn

Check INLET port filter, Clean or replace

Rebuild compressor, replace piston seal

Unit does not pull a vacuum

Loose hose connections on Inlet Side

Compressor seals are worn

Tighten Hose connections

Rebuild compressor, replace piston seal

Check power cord to ensure properly 
plugged into power source and IEC inlet

Unit not properly plugged in or no 
power at power source

Check core depressor on connecting 
hoses

Valve core on system being recovered 
not fully depressed

RED LED CODE

FAULT INDICATED

POSSIBLE SOLUTION

3 Flashes

Excessive pressure in recovery tank.  Replace recovery tank.

Pressure on the discharge of the unit exceeded 550 PSIG. Check 
to make sure all valves in the discharge pathway are open.  
Once corrected, the pressure switch will reset.  If equipped with 
manual high pressure switch, push reset button.

High Pressure Swich as been 
activated

4 Flashes

Let cool down for 15 minutes and restart.

Motor Overload

5 Flashes

Check to see if power source is In the range of the nameplate 
rating.

Low Voltage Detected

6 Flashes

Check to see if power source is In the range of the nameplate 
rating.

High Voltage Detected

Содержание BVV2CY

Страница 1: ...In Class I and Ii Division 2 and Class Iii Divisions 1 And 2 Hazardous Classified Locations Model BVV2CY Model BVV4CY Only qualified personnel trained in the handling of flammable and non flammable re...

Страница 2: ...hazards Read and understand this operator s manual and all safety materials before using Failure to properly use this unit correctly can result in personal injury and or equipment damage TABLE OF CONT...

Страница 3: ...may contain liquid refrigerant under pressure Contact with refrigerant may cause frostbite or other related injuries Wear proper personal protective equipment such as safety goggles and gloves When d...

Страница 4: ...required DANGER EXPLOSION RISK Do not mix flammable refrigerants with air All precautions must be taken to eliminate the mixing of air with flammable refrigerants including monitoring the recover cyli...

Страница 5: ...x WC TW Turn on the scale and tare to Zero Place storage tank on scale Read the weight Compare that to the MTW calculated above If the scale weight is below MTW you still have storage capacity you hav...

Страница 6: ...0 amps 2 4 350 PSIG 32F to 105F 18 0 x 10 0 x 12 0 25 0 lbs 35 0 lbs Motor Type Maximum Current Number of Cylinders High Pressure Cutout Operating Temperature Range Dimensions Weight Plug and Play Un...

Страница 7: ...omp Module 1 2 NPT Discharge Port 1 2 NPT Suction Port LED IEC Socket PCB Module High Pressure Switch BVV4CY BVV2CY START STOP button 2 CYL Comp Module LED IEC Socket High Pressure Switch 3 8 JIC Disc...

Страница 8: ...scharge valve seats Warranty may be void if oil and resins are present 3 Plug unit into either a 115V or 230V power source The Indicator LED will flash GREEN 4 Once it is determine the unit is to begi...

Страница 9: ...r at power source Check core depressor on connecting hoses Valve core on system being recovered not fully depressed RED LED CODE FAULT INDICATED POSSIBLE SOLUTION 3 Flashes Excessive pressure in recov...

Страница 10: ...10 ELECTRICAL PLUMBING SCHEMATICS PARTS LIST BVV 1251 Frontenac Road Ste 150 Naperville IL 60563...

Отзывы: