8 | Parameter Description
28 / 56
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
0: Not used
1: Automatic voltage boost (improves motor torque).
P1.16 Show All Parameters
0: Only Basic group (and PI Control if function is used)
1: All parameters groups are visible.
P1.17 Service Counter
After 8000 operating hours the machine must be maintained. After maintenance, reset
the service counter to 0.
8.2 Advanced Settings
P2.2 to P2.8 Preset Speed 1 to 7
You can use the preset frequency parameters to define certain frequency references
in advance. These references are then applied by activating/inactivating digital inputs
connected to parameters P4.8, P4.9 and P4.10 (binary code). The values of the preset
frequencies are automatically limited between the minimum and maximum frequen-
cies.
Required Action
Activated Frequency
P4.10
P4.9
P4.8
0
0
1
Preset speed 1
0
1
0
Preset speed 2
0
1
1
Preset speed 3
1
0
0
Preset speed 4
1
0
1
Preset speed 5
1
1
0
Preset speed 6
1
1
1
Preset speed 7
P2.10 Deceleration Time 2
Ramp 2 is activated through digital input defined in P4.11 or through fieldbus. Auto-
matic selection based on output frequency is also available (P2.12).
P2.11 Accel 1 to Accel 2 Transition Frequency
If P2.11 is not 0, acceleration time 2 is activated when output frequency is higher than
the value.
P2.12 Decel 1 to Decel 2 Transition Frequency
If P2.12 is not 0, deceleration time 2 is activated when output frequency is higher than
the value.
P2.13 S Ramp Shape 1