Parameter Overview | 7
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
23 / 56
Code Parameter
Min. Max.
Unit Default ID
Description
P9.15 Response to fieldbus
fault
0
2
733
See P9.3
P9.18 Response to STO dis-
able
0
3
1876 0 = No action
1 = Warning
2 = Fault, not stored in history menu
3 = Fault, stored in history menu
P9.19 Response to input phase
fault
0
2
1877 See P9.3
P9.20 Input phase fault
maximum ripple
0
75
1893 0 = Internal value
1 = max. sensitivity --
►
75 = min. sensitivity
P9.21 Motor temperature
initial mode
0
2
1891 0 = Start from minimum
1 = Start from constant value
2 = Start from last value
P9.22 Motor temperature
initial value
0
100
%
1892 Initial value (P9.21 = 1)
or factor for
previous value (P9.21 = 2)
P9.24 Output phase fault
0
2
702
See P9.3
P9.25 Service time
1
65535
h
1902 Determine the service time
7.12 Autoreset: Menu PAR G10
Code Parameter
Min. Max. Unit Default ID
Description
P10.1 Automatic fault reset
0
1
1
731
0 = Disabled
1 = Enabled
P10.2 Wait time
0.1
10
s
0.5
717
Wait time before the first reset is ex-
ecuted.
P10.3 Trial time
0
60
s
30
718
When the trial time has elapsed and the
fault is still active, the drive will trip to
fault.
P10.4 Automatic reset trials
1
10
3
759
Total number of trials (irrespective of fault
type)
P10.5 Start function
0
2
0
719
The start mode of automatic reset is se-
lected with this parameter:
0 = Ramp
1 = Flying start
2 = According to parameter P1.13
P10.6 Undervoltage fault
0
1
1
720
0 = Fault, stored in fault memory
1 = Fault, deleted from fault memory after
reset
P10.7 Overvoltage fault
0
1
0
721
See P10.6
P10.8 Overcurrent fault
0
1
0
722
See P10.6
P10.9 Motor over-temperature
fault
0
1
0
725
See P10.6
P10.1
0
Underload fault
0
1
0
738
See P10.6
7.13 Fieldbus: Menu PAR G11