Parameter Overview | 7
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
15 / 56
7.3 Basic Parameters: Menu PAR G1
Code Parameter
Min.
Max.
Unit Default ID
Description
P1.1
Min. frequency
0
P1.2
Hz
40*
101
Minimum allowed frequency reference
P1.2
Max. frequency
P1.1
320
Hz
140*
102
Maximum allowed frequency reference
P1.3
Acceleration time 1
1.0
3000
s
2.0
103
Time from 0 to maximum frequency
P1.4
Deceleration time 1
0.1
3000
s
2.0
104
Time from maximum frequency to 0
P1.5
Current limit
0.2xI
H
2xI
H
A
0*
107
Maximum motor current from frequency
inverter
P1.6
Motor nominal voltage
180
500
V
0*
110
Find this value U
n
on the name plate
from the motor. This parameter sets the
voltage at field weakening point to
100%* U
nMotor
.
Note: also used connection Delta/Star.
P1.7
Motor nominal frequency 8
320
Hz
140*
111
According motor data
P1.8
Motor nominal speed
24
20000 rpm
4200*
112
According motor data
P1.9
Motor nominal current
0.2xI
H
2xI
H
A
0*
113
According motor data
P1.10 Motor Cos Phi
0.30
1
0.93*
120
According motor data
P1.11 Control Place
0
2
0
125
Run and direction control:
0 = I/O terminals
1 = Keypad
2 = Fieldbus
P1.12 Frequency reference
source
0
5
0
1819 Selection of reference source:
0 = Analogue input 1
1 = Analogue input 2
2 = PID reference
3 = Motor potentiometer
4 = Keypad
5 = Fieldbus
P1.13 Start function
0
1
0
505
0 = Ramping
1 = Flying start
P1.14 Stop function
0
1
0
506
0 = Coasting
1 = Ramping
P1.15 Torque boost
0
1
0
109
0 = Not activated
1 = Auto torque boost
P1.16 Show all parameters
0
1
1
115
0 = Only basic parameter
1 = All groups
P1.17 Service counter
0
65535 h
0
1899 Service counter
*depending on motor and machine sizes