5 | Installation
20 / 36
Instruction Manual Supplement DOLPHIN VL Systems ATEX_EN_en
Switch point :
TSA
For temperature class T4 – 5°K less than temperature class or 20°K less than the liquid
boiling point whichever is lowest.
For temperature class T5 - maximum of 50°C or 20°K less than the liquid boiling point
whichever is lowest.
TSA1
Temperature of operating liquid depends on temperature of fresh cooler operating liquid
available.
Minimum operating liquid temperature 10°C for water or operating liquid melting point
plus 10°K.
Maximum operating liquid temperature 50°C or operating liquid boiling point less 20°K,
whichever is lowest.
5.4.3 Wiring Diagram Pilot Solenoid for Pneumatic Valve
Part no. :
VAOS/2761
Supplier reference :
Pneumatic angle seat piston valve fitted
with NAMUR mounted solenoid control
valve.
Electrical data :
ATEX Ɛx Certified : II 1GD Ex ia IIC T6 Ga
For intrinsically safe circuit, maximum val-
ues
U
i
= 28 VDC, I
i
= 115 mA, L
i
~0, C
i
~0
Minimum I
i
= 85 mA
ATEX Ɛx Certified : II 1GD Ex ia IIB T6 Ga
For intrinsically safe circuit, maximum val-
ues
U
i
= 32 VDC, I
i
= 195 mA, L
i
~0, C
i
~0
Ambient temperature range : -40°C …
+50°C
2 (-)
1 (+)
PE
5.4.4 Wiring Diagram Level Switches
Part no. :
0652700909
Supplier reference :
WIKA: BGU-E-1 PVC-blau
Electrical data :
Ɛx II 1G Ex ia IIC T6-T3
For intrinsically safe circuit Ex I, maximum
values
U
i
= 30V, I
i
= 100mA, P
i
= 1W, C
i
= 0, L
i
= 0
Integral 1m PVC cable provided with each
switch.
Ambient temperature range -40°C … +55°C,
IP 65
Brown
black
blue
Содержание DOLPHIN VL 0100 A
Страница 34: ...Note...
Страница 35: ...Note...