INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS - BAR TO GROUND ROD
BR-9
Insert end of ground rod
even with upper edge of
bus bar. Pack ground
rod opening with packing
material when run bus is
3" or wider.
BR-99 for M-3729
Place ground rod and bus
bar into mold as shown.
BR-25
Insert ground rod and bus
bar as shown. Gap bars
1/8" under center of tap
hole.
BR-3
Place ground rod and bus bars into
mold as shown.
BR-99 for M-3776
Place ground rod and bus
bar into mold as shown.
BR-29
Place end of bar under center of
tap hole. With mold closed, insert
ground plate.