background image

14 

16.

 

Flue Gas Analysers – Installation & Servicing Facts 

 

 

Please read this sheet even if you have fitted our fires before.  
 

 

Please leave this sheet with the customer as reference for future servicing of the appliance.  

 

 

Please explain to the customer how the fire works and the details and facts listed on this sheet, 
particularly what the catalyst does and doesn’t do.  
 

 

If you have any doubts about the test procedure please visit our website or call our technical 
help line 

 

Testing – Points to note…  
 

 

Before  testing  ensure  that  the  room  size  is  correct  for  the  heat  output  of  the  fire.  30cu³  for 
2.5kw output, 40cu³ for 3.5kw and 50cu³ for 4.5kw.  

 

 

In  all  installations  regardless  of  room  size  there  must  be  an  air  vent  positioned  at  least  one 
metre from the fire at either high or low level through an outside wall providing 100cm² of free 
air.  (For  the  Republic  of  Ireland  2  vents of  not  less  than 60cm²  must be  provided  at high  and 
low level, with minimum vertical separation of 1.6m). 

 

 

The  analyser  used  must  be  manufactured  to  BS7967  and  the  test  must  be  carried  out  in 
accordance with BS5871 Pt 4 

 

 

The  catalytic  converter  needs  heat  to  work,  therefore  before  you  start  testing;  the  fire  must 
have been lit and burning on full for at least 15 mins.  

 
There are two tests to carry out. A Co / CO² ratio test and a room centre CO test.  
 

1.

 

The first test is the CO / CO² ratio test and should be carried out at the fire exhaust vent, do not 
stick the probe of the analyser in through the grill but move the probe back and forth 1 inch in 
front of the outlet grill. (We use a piece of perforated 8mm pipe attached to the analyser with 
flexible rubber tube). You should record a ratio of no more than 0.002 % (20ppm CO to 1% Co²). 
It is advisable to have a high sample of CO as this will improve the test 

 

2.

 

The second test is the room centre CO test. You should stand in the room centre with the probe 
at waist height and read the level of CO; this should be no more than 9ppm over ambient peak. 
Please record these readings on the customers guarantee card.  

 
Our Flueless fires also contain the following safety devices (an ODS (Oxygen Depletion Sensor) and FSD 
(Flame  Supervision  Device).  Point  out  to  the  customer  that  unfortunately  these  are  not  found  on  all 
gas hobs; which are also flueless devices)

 

 
 
 
 
 
 
 

Содержание G4121

Страница 1: ...HESE INSTRUCTIONS WITH THE USER Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4121InstUser...

Страница 2: ...GHTING EASIER BURLEY APPLIANCES IS THE ONLY COMPANY TO BENCH RUN AND THOROUGHLY TEST EVERY SINGLE GAS FIRE IT PRODUCES BURLEY IS IN THE UNIQUE POSITION OF KNOWING THAT EVERY APPLIANCE LEAVES THE FACTO...

Страница 3: ...ld cease and be replaced with the ticking sound of the spark igniter When the pilot flame is lit the igniter will stop another acoustic signal will confirm the pilot has been established if the pilot...

Страница 4: ...unit to its original position REPLACE THE HEATSHIELD over the unit Press here and slide down CAUTION With the exception of battery replacement the battery holder must be located within the heat shiel...

Страница 5: ...owly anticlockwise to the ignition position A click will be heard and the pilot under right side of fuel bed should light If it does not repeat the operation a few times to purge any air in the pipe C...

Страница 6: ...gory I2H I3P Supply Pressure 20mBar 37mBar Inlet Pressure 20mBar 37mBar Heat Input Net High 3 5kW 3 5kW 250g h Low 1 7kW 1 7kW 120g h Inlet Connection 8mm Compression 8mm Compression Injector stereo 3...

Страница 7: ...combustible surface 3 8 No furniture soft furnishings decorations wall coverings or curtains must be within 1 metre of the appliance and its convection outlets 3 9 The appliance must not be installed...

Страница 8: ...fore cleaning or maintenance switch fire OFF and allow to cool 4 7 Any purpose provided ventilation should be checked regularly to ensure it is free from obstruction 5 Hearths floor protection and car...

Страница 9: ...igid tubing such as copper pipe Before working on pipework plug open ends A servicing isolator is supplied with the appliance and this should be used to permit disconnection for servicing etc All gas...

Страница 10: ...fitted similar to the Natural Gas fire The base log locates onto the burner and the front log is pushed to the extreme left hand side as shown Take care to locate them correctly to ensure clean combus...

Страница 11: ...k Failure The gap between the pilot electrode and the pilot should be 3 5 4 5mm and normally adjustment is not necessary Check the fire lights at least 3 times out of 5 attempts Visually check that th...

Страница 12: ...outlet Ratio of CO CO2 should be less than 0 002 within 30 minutes 20ppm CO per 1 CO2 A reading of CO in the room centre should give a rise of less than 9ppm over ambient peak reading Light the fire u...

Страница 13: ...0 The appliance must not be used in rooms where the atmosphere is likely to contain water or chemical vapours which may adversely affect the appliance or its finish 11 Do not use whilst painting decor...

Страница 14: ...test must be carried out in accordance with BS5871 Pt 4 The catalytic converter needs heat to work therefore before you start testing the fire must have been lit and burning on full for at least 15 mi...

Страница 15: ...ult the relevant manufacturer Only use replacement catalyst supplied by Burley If you or the customer detects any odours from the fire please remember that the catalytic convertor is not an air filter...

Страница 16: ...st over a reasonable period of time so that the capacity of the meter is used On low Input appliances such as our flueless this is even more critical because uncertainties can creep in It is worth mea...

Страница 17: ...y gas appliances must be serviced every year The appliance has not been subject to misuse accident or repaired or fitted by anyone other than Gas Safe registered installer formerly CORGI or our own en...

Страница 18: ...ling WEEE Dispose of electrical equipment in an environmentally correct manner When disposing components containing Refractory Ceramic Fibres RCF we recommend that the items are not broken up but are...

Страница 19: ...19...

Страница 20: ...fires are protected by UK patents 2193802 2240620 and 2256920 Other Patents Pending Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Tel 01572 725570 Fax 01572 724390 www burley co uk Email...

Отзывы: