12
TechnicalData
6.4.2. rating plate of the control cabinet
model
8611 Panel 24VDC
00210206
W16LU
Prozessregler
S/N xxxxxx
Assembly model
- Panel (control cabinet
Controller type
Power supply voltage
Controller design
Serial number
Manufacturer's code
Order part number
Example:
Fig. 4: Example: Rating plate of the control cabinet model
6.5.
electrical data
Operating voltage:
24 V DC ±10 %,
filtered and controlled
Power consumption
without load: approx. 2 W
with load: maximum 48 W
100 % ED: 36 W
Controller sampling rate:
300 Hz
6.5.1. inputs
set-point value
Standard 4 - 20 mA
Input impedance: 70
Ω
Resolution:
5.5 µA
Standard 0 - 10 V
Input impedance: 11.5 k
Ω
Resolution:
2,5 mV
sensors
Standard 4 - 20 mA
Input impedance: 70
Ω
Resolution:
5.5 µA
Frequecy
Input 1 External sensor
Frequency range: min. 0.25 Hz / max. 1 kHz
Input resistance: > 1 k
Ω
Signal types:
Sine, rectangle, triangle
(> 3000 mVss, max. 30 Vss)
Input 2 Internal Hall sensor
Frequency range: min. 0.25 Hz / max. 1 kHz
(only in conjunction with Bürkert
flow-rate fitting Type S030)
Pt 100
(2-wire) Measuring range:
0 °C ... 200 °C
Measured current:
1 mA
Measuring error:
< 0.5 °C