41
Assembly
Type 8792, 8793 REV.2
→
To achieve the best-possible control accuracy, set the external position sensor such that the past to be
detected corresponds to the signal range 4...20 mA (only if the external position sensor includes this
function).
→
In the
ADD.FUNCTION
menu activate the
POS.SENSOR
function. Then select
POS.SENSOR
in the main
menu and set
ANALOG
(see chapter “16.1.21 POS.SENSOR” on page 118.
→
Run the
X.TUNE
function.
11.5
Pneumatic connection
11.5.1
Safety instructions
DANGER
Risk of injury from high pressure in the system.
▶
Before loosening lines and valves, turn off the pressure and vent the lines.
WARNING
Risk of injury from improper installation.
▶
Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury due to unintentional switching on of the plant and uncontrolled start-up.
▶
Secure the device against accidental activation.
▶
Following installation, ensure a controlled restart.
Working connection 2
(connection: A2)
Pressure supply connection 1.4...7 bar
(connection: P)
Working connection 1
(connection: A1)
Air exhaust connection
Figure 19:
Fluid installation / Location of the connections