35
Functions
CHARACT
10.1.3.
-
Transfer characteristic between input signal
(position set-point value) and stroke
Characteristic (customer-specific characteristic)
This function can be used to activate a transfer characteristic with respect to set-point value (set-point position)
and valve stroke for correction of the flow or operating characteristic.
The transfer characteristic can be changed via the communications software only.
Factory settings: DIP switch 3 set to OFF (linear)
DiP switches Position
Function
3
ON
Correction characteristic for adjustment of the operating character-
istic (linearization of the process characteristic
CHARACT
)
9)
OFF
Linear characteristic
DIP switch 3
Table 16:
The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the correction characteristic (
CHARACT
) which are changed via the communica-
tions software are not active unless DIP switch 3 in the positioner is set to ON.
Characteristics which can be selected via the communications software:
Characteristic
Description
Linear
Linear characteristic
1 : 25
Equal percentage characteristic 1 : 25
1 : 33
Equal percentage characteristic 1 : 33
1 : 50
Equal percentage characteristic 1 : 50
25 : 1
Inversely equal percentage characteristic 25 : 1
33 : 1
Inversely equal percentage characteristic 33 : 1
55 : 1
Inversely equal percentage characteristic 55 : 1
FREE
User-defined characteristic, freely programmable via nodes
Selection of characteristics
Table 17:
A detailed description of the characteristics can be found in the operating manual for the communications
software for positioners.
9)
The characteristic type can be changed via the communications software only.
english
Type 8791
Содержание 8791
Страница 184: ...184 accessoires Type 8791 français ...
Страница 185: ......
Страница 186: ...www burkert com ...