System
Parameters
Software options
Options list
Activate option
This is
when the
device is be-
ing parame-
tered............
....................
This is
when the
device is be-
ing parame-
tered............
....................
ENTERING
PID
Datalogger
Dosing
Flow
Concentration
ETH. Protocols
When an option is ticked, it is activated in the device.
OPTIONS LIST:
read the options available, whether or not activated on the device:
-
PID:
enables configuring of a PID function on the device; See section 8.10.15.
-
DATALOGGER
: enables the recording of process data; See section 8.10.19.
-
DOSING
: enables configuring of the "Time dosing" and "Volume dosing" functions; See sections 8.10.16
and 8.10.17. This option automatically activates the "FLOW" option below.
-
FLOW
: the "Flow" and "Totaliser" process inputs are available in the "PV" list on the main board "M0:MAIN"
and the input modules "Mx:Inputs"; See section 8.16
.
-
CONCENTRATION
: the concentration tables for a number of solutions are available in the menu "Param-
eters" -> "Mx:Conductivity" -> "Concentration"; See section 8.10.26
-
ETHERNET PROTOCOLS:
enables configuring of the ethernet protocols (Modbus TCP, PROFINET or Eth-
erNet/IP) on a device with an Ethernet module. The default ethernet protocol activated is Modbus TCP; See
section 8.10.24.
ACTIVATE OPTION:
enter the activation code for an option.
8.10.5 Saving the settings on the memory card
This function is used to save, on the memory card, the user settings of the main board M0 and of all the modules
fitted ("Parameters" menu).
• Only authorized personnel may insert in or remove a memory card from the reader/recorder.
• To ensure the tightness of the device, tighten the 4 screws of the cover in a crosswise manner with a
torque of 1.4 N·m ± 20 % (1,03 lbf·ft ± 20 %).
• Data can only be saved if the "datalogging" function is deactivated. See sections 8.10.4 and 8.10.19.
• The software options activated on the device (see section 8.10.4) cannot be transferred.
Refer to section 8.9 to access the "Parameters" menu.
This is
when the
device is be-
ing parame-
tered............
....................
This is
when the
device is be-
ing parame-
tered............
....................
System
Parameters
Save settings
M0:MAIN
Mx:
... 1)
1)
The choices offered depend on the modules fitted. See section 8.16 Process inputs or values or process value network
If an error message is displayed, refer to section 9.3.7.
84
Adjustmentandcommissioning
Type 8619
English
Содержание 8619 multiCELL WM AC
Страница 6: ...6 English ...
Страница 12: ...12 Type 8619 English ...
Страница 24: ...24 Type 8619 English ...
Страница 40: ...40 Type 8619 English ...
Страница 70: ...70 Installation and wiring Type 8619 English ...
Страница 180: ...180 Type 8619 English ...
Страница 192: ...192 Type 8619 English ...
Страница 193: ......
Страница 194: ...www burkert com ...