8.11.2 Modifying the Calibration menu access code
Refer to section 8.9 to access the "Calibration" menu. If the default access code "0000" is kept, the device does
not request it to access the Calibration menu.
Enter the
new
calibration menu
access code
Confirm the new
code
Calibration
System
Code
0***
Confirm code
0***
8.11.3 Adjusting the current outputs
Ensure that Hold mode is disabled before adjusting the current outputs: icon
appears on the
display.
Refer to section 8.9 to access the "Calibration" menu.
Calibration
M0:Outputs
AO1/AO2
4mA
20mA
ENTERING
ENTERING
Mx:Outputs
4 MA
: Adjust the offset of the current output.
When the "4mA" function is selected, the 8619 generates a current of 4 mA:
→
measure the current emitted by the 4...20 mA output using a multimeter;
→
enter the value given by the multimeter.
20 MA
: Adjust the span of the current output.
When the "20mA" function is selected, the 8619 generates a current of 20 mA:
→
measure the current emitted by the 4...20 mA output using a multimeter;
→
enter the value given by the multimeter.
133
Adjustmentandcommissioning
Type 8619
English