P
1
and P
2
are the values associated with a current of 4 mA or 20 mA respectively.
If P
1
is higher than P
2
, the signal is inverted and the range P
1
– P
2
corresponds to the range for the
20...4 mA current.
mA
0
20
4
P
2
P
1
Fig. 84 : 4...20 mA current depending on the PV selected
FILTER
: Choose the level of attenuation for the fluctuations of the current value for each current output. See
DIAG. EVENT
: Choose to emit a current of 22 mA on the current output selected when an "error" event related
to diagnostics (see sections 8.12.2 to 8.12.6) is generated by the 8619 or allow the current output to operate
normally (choose "none").
See also "If you encounter problems" in section 9.3.
119
Adjustmentandcommissioning
Type 8619
English