Maintenance and troubleshooting
Type 8098
19.9.7
Message "Test mode activated"
Message
Test mode activated
Symbol displayed
Possible cause
The test of an output has been started by the user.
What to do?
→
If needed, complete the test.
19.9.8
Message "Simulation mode active"
Message
Simulation mode active
Symbol displayed
Possible cause
A measurement value is being simulated.
What to do?
→
As soon as the simulation is completed, the message is reset.
19.10
Messages due to the monitoring of process values
19.10.1
Message "Flow rate too high"
Message
Flow rate too high
Symbol displayed
Possible cause
The flow rate value is higher than the permitted maximum error value set in
13.4.7 Changing the error limits, the warning limits and the hysteresis
What to do?
As soon as the flow rate returns to within the permitted range, the error is
automatically reset.
Message
Flow rate too high
Symbol displayed
Possible cause
The flow rate value is higher than the permitted maximum warning value
set in chpt.
13.4.7 Changing the error limits, the warning limits and the hys-
teresis of the volume flow rate
What to do?
As soon as the flow rate returns to within the permitted range, the warning is
automatically reset.