Outputs - Parameter
Type 8098
16.5
Setting the parameters of a digital output
By default, the device has 1 digital output and 1 analogue output,
Output 1:digital
and
Output 3:analog
.
You can change the type of the outputs: see chpt.
16.2.
A digital output can be configured:
• as an on/off output
•
or, to switch depending on two threshold values
•
or, as a frequency output
•
or, as a pulse output
Default parameters of output 1 after activation as digital output:
Parameter
Default value
Mode
Pulse
Max. pulse time
65 ms
Max. frequency
2000 Hz
Pulse mode
Pulse/Volumen
Pulses/volumen
Tube diameter DN8 or 1/2'': 2000 pulses per volume unit
Tube diameter 3/8'': 4000 pulses per volume unit
Other tube diameters: 100 pulses per volume unit
Inverted
No
Table 18:
Default parameters of the digital output
Default parameters of output 3 after activation as digital output:
Parameter
Default value
Mode
On/Off
Inverted
No
Delay
0.000 s
Table 19:
Default parameters of the digital output