SAW sensor - Parameter
Type 8098
13.9.5
Deactivating the monitoring of the acoustic transmission
factor
By default, the acoustic transmission factor values are not monitored.
If the monitoring of the acoustic transmission factor is active, do the following to deactivate it:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Add. meas. values
→
Acoustic transmission factor
→
Limits
→
Active
→
Select
No
.
The monitoring of the acoustic transmission factor is inactive.
13.9.6
Resetting the default values of the error limits, the warning limits
and the hysteresis of the acoustic transmission factor
The default values of the error limits, the warning limits and the hysteresis of the acoustic transmission
factor are the following:
• high error value: 195%
• low error value: 5%
• high warning value: 190%
• low warning value: 10%
• value of the hysteresis: 1%
To reset the default values of the error limits, the warning limits and the hysteresis of the acoustic trans-
mission factor, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Add. meas. values
→
Acoustic transmission factor
→
Limits
→
Reset to default
→
Finish
The limit values and the hysteresis value are reset.
English