42
Functions
Input of the freely programmable characteristic
The characteristic is defined via 21 supporting points which are evenly distributed over the set-point range
from 0 to 100%. Their spacing is 5%. A freely selectable stroke (setting range 0...100%) can be assigned to
each supporting point. The difference between the stroke values of two adjacent supporting points must not
be greater than 20%.
Example of a programmed characteristic
Valve stroke [&]
Standard signal
[%]
10
20
30
40
50
60
70
80
90
100
10 20 30 40 50 60 70 80 90 100
0
4...20 mA
0...20 mA
Fig. 16:
Example of a programmed characteristic
10.1.4
INPUT
-
Input of standard signal (only variant without fieldbus
communication)
This function is used to set the input signal for the set-point value.
Factory setting: 4...20 mA, 4 conductor
Other settings: 4...20 mA, 3 conductor
0...20 mA, 4 conductor
0...20 mA, 3 conductor
Type 8791, REV.2
english
Содержание 8791 REV.2
Страница 80: ...80 Type 8791 REV 2 english ...