39
Functions
10.1.2
CUTOFF
-
Sealing function for the positioner
This function ensures that the valve is tightly closed outside the control range.
Closed-loop control mode resumes with hysteresis of 1%.
Factory setting: DIP switch 2 to OFF (no sealing function)
DIP switch
Position
Function
2
ON
Sealing function active. The valve completely closes below
2%
19)
and opens above 98% of the set-point value (
CUTOFF
)
OFF
No sealing function
Table 21:
DIP switch 2
The limits for the position set-point value in per cent can be changed with the communication software.
The switch position of the DIP switch in the positioner takes precedence over the communication
software, i.e. sealing function (
CUTOFF
) settings which are changed with the communication
software are only active if DIP switch 2 is set to ON in the positioner.
Valve stroke
[%]
adjustable from 75 to 100%
Set-point
value [%]
adjustable from 0 to 25%
Fig. 14:
CUTOFF diagram
19) Factory setting, can be changed using communication software.
Type 8791, REV.2
english