24
Technical data
8.4
Type label
Made in Germany
C
US
®
8791 24 V DC 5 W
Remote IO-Link REV.2
P=1.4...7 bar IP65/67
Tamb –10...+60°C
S/N 1000
00123456 W17MA
Type
Operating voltage
Nominal power
Device variants, communication,
version
Operating pressure, degree of protection
Ambient temperature
CE marking
CSA approval mark (for Canada
and USA)
Order number, manufacture code
Barcode
Serial number
Fig. 6:
Type label (example)
8.5
Electrical data
8.5.1
Electrical data, without fieldbus communication
Protection class
III according to DIN EN 61140 (VDE 0140-1)
Connections
2 cable glands (M20 x 1.5)
with screw-type terminals 0.14...1.5 mm
2
or
circular plug-in connectors (M12, 8-pin)
Operating voltage
24 V DC ±25% max. residual ripple 10%
Current consumption
max. 190 mA
Power consumption
max. 3.5 W
Input resistance
for set-point value signal
75
Ω
at 0/4...20 mA/Resolution 12 bit
Analogue position feedback
max. burden/load
for current output 0/4...20 mA
560
Ω
Inductive proximity switches
100 mA current limit
Digital input
0...5 V = logical “0”, 10...30 V = logical “1”
(Invert the logic with software)
(Input current < 6 mA)
Communication interface
Connection to PC using USB büS interface set
Communication software
Bürkert Communicator
Type 8791, REV.2