49
AS-Interface installation
Bit configuration
1. Output set-point value (Value range 0 – 10.000, is equivalent to 0 – 100 %)
2. Input feedback
18)
(Value range 0 – 10.000, is equivalent to 0 – 100 %)
Byte 2
Byte 1
0
0
D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
parameter bit
p3
p2
p1
p0
Output
not used
not used
not used
not used
Table 23:
Bit configuration
11.4. communication sequence for the version s-7.a.5
profile
1. Following start-up, the AS-Interface master (from master class 4) automatically replaces the ID object with the
S-7.A.5 slave.
S-7.A.5 slave replies with 6 bytes
1. Byte: Code
=
80 dez
2. Byte: Vendor ID (high)
= 120 dez
3. Byte: Vendor ID (low)
4. Byte: Device ID (high)
=
1 dez
5. Byte: Device ID (low)
6. Byte: 1 word
1 word input
=
34
dez
or with 2 Byte (Read Response not OK)
1. Byte: Code
= 144 dez
2. Byte: Error Code
=
0
1
2
3
4
dez (no error)
dez (illegal index)
dez (illegal length)
dez (request not
implemented)
dez (busy)
Master transmits 3 bytes:
1. Byte: Code
= 16 dez
2. Byte: Index
=
0 dez
3. Byte: Length =
5 dez
2. Then the following cyclical commands can be used:
Code = 0 (get cyclic data from Slave)
→
for feedback 0 – 100 %
Code = 1 (put cylic data to slave)
→
for set-point value 0 – 100 %
18)
Only for version with S-7.A.5 profile
English
Type 8694