Control and display elements
7.6.
error messages
7.6.1.
error messages in manual and auTOmaTic operating
statuses
Display
Cause of fault
remedial action
LED 1 (red)
on
Checksum error in data memory
→
Data memory defective
→
The device automatically switches to an older
(possibly not current) data record.
Not possible, device defective
Table 11:
Error messages in the operating statuses
7.6.2.
error messages while the
X.TUNE
function is running
Display
Cause of fault
remedial action
LED 1 (red)
on
No compressed air connected
Connect compressed air
Compressed air failure while the
X.TUNE
function was running
Check compressed air supply
Actuator or control system deaeration side
leaking
Not possible, device defective
Control system aeration side leaking
Not possible, device defective
Table 12:
Error messages for the X.TUNE function