Technical data
6.8.
factory settings of the positioner
Functions can be activated via DIP switches:
function
parameter
Value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Select characteristic
FREE
5)
DIR.CMD
Effective direction set-point value
rise
Table 4:
Factory settings - Functions I
Functions can be activated via communications software:
function
parameter
Value
INPUT
Set-point value input
4 ... 20 mA
DIR.ACTUATOR
Effective direction actual value
rise
SPLITRANGE
Function deactivated
Signal split range below
Signal split range above
0 %
100 %
X.LIMIT
Function deactivated
Stroke limit below
Stroke limit above
0 %
100 %
X.TIME
Function deactivated
Actuating time Open
Actuating time Closed
(1 s) values determined by
X.TUNE
(1 s) values determined by
X.TUNE
After implementation of
RESET
: 1 s
X.CONTROL
Deadband
Open amplification factor
Close amplification factor
1,0 %
(1) values determined by
X.TUNE
(1) values determined by
X.TUNE
After implementation of
RESET
: 1
SAFE POSITION
Safety position
0 %
SIGNAL ERROR
Function deactivated
Sensor break detection set-point value
OFF
BINARY INPUT
Binary input function
Operating principle of binary input
Safety position
Normally open
OUTPUT
(optional)
Norm signal output: Parameter
Norm signal output: Type
Position
4 – 20 mA
Table 5:
Factory settings Functions II
5)
Without change to the settings via the communications software a linear characteristic is stored in FREE.