158
Replacement of Components and Modules
24.2
Changing the electronic module
NOTE!
Electrostatic sensitive components/modules!
• The device contains electronic components which react sensitively to electrostatic discharge (ESD). Contact
with electrostatically charged persons or objects may be hazardous to these components. In the worst
case scenario, they will be destroyed immediately or will fail after start-up.
• Observe the requirements in accordance with DIN EN 61340-5-1 to minimise or avoid the possibility of
damage caused by sudden electrostatic discharge!
•
Also ensure that you do not touch electronic components when the operating voltage is on!
Removal procedure:
→
Open the housing following the instructions in chapter
“8 Opening and Closing the Housing”
→
If necessary, mark the electrical connections to ensure correct assignment during reinstallation!
→
If necessary, note the position of the 4 DIP switches for the set colour code and on the DeviceNet
electronic module the DIP switches (8-switch block) for Baud rate and address. On the AS-i electronic
module, note the AS interface address and the jumper positions (power supply to AS interface).
→
If required, read out and note special settings by the PC service program.
→
Loosen all electrical connections on the electronic module (plug-type connections, screw-type terminal
connections).
→
Loosen the screw-type connection (Torx T10 screw) of the electronic module and store the screw in a safe
place.
→
Carefully press the electronic module forwards so that the contact pins on the position measuring
system are exposed.
→
Carefully lift the electronic module upwards.
4 DIP switches for
colour coding
Fastening screw
(Torx 10)
Connection for the position
measuring system's contact
pins
Electronic module,
complete (lower part cast,
ready for installation)
Plug-in connectors
for valves V2 and V3
Jumper for AS interface
power supply
Plug-in connector for valve
V1
Fig. 51:
Electronic module (here example of AS interface)