CALIBRATION
From the main menu, press
CONFIG then CALIBRATE.
Find the desired channel
using the scroll buttons as
needed then press the
channel to select it.
Press CALIB to show the calibration screen for the selected
channel.
Use the keypad to enter the actual value as read from the local meter, then
press ENTER.
For diagnostic purposes, the raw sample voltage (or virtual channel value)
will show below the meter window.
Calibration can only be performed on the local site.
SYSTEM MENU
Press
CONFIG
from the main menu to select the
CONFIGURATION
sub-
menu then press
SYSTEM.
CLOCK
Press CLOCK to display the time and date settings.
Press DATE, TIME, or TIME ZONE to change the value shown.
Press the field to be changed then use the keypad to enter the correct
value.
Repeat until all fields are correct then press ENTER
At least 250mV of sample
voltage is required in order to
calibrate channels. Note that
channels configured for millivolt,
degree or virtual input types
cannot be calibrated.