Bulletin T-TS3 Скачать руководство пользователя страница 1

Bulletin T-TS3

Specifications - Installation and Operating Instructions

 

Coastal MK II 

Digital T

hermostat/Thermometer

The 

Coastal MK II

 Digital T

hermostat

is the ideal

control for on/off heating or cooling applications. This generation
of controls has field selectable engineering units and
temperature probe types in order to reduce the combination of
parts that need to be stocked. A built in real time clock is used
for HACCP logging of temperature alarms caused by
temperatures outside of their set limits or loss of power. For
refrigeration applications, the defrost cycle can be initiated
based on time or using the front panel keys. For programming
multiple units, the model TS2-K configuration key can be used
to quickly download parameter settings.

INSTALLATION

NOTE: Unit must be mounted away from vibration, impacts, water and
corrosive gases.

• Cut hold in panel 71 x 29 mm (2.80 x 1.14 in).
• Use the supplied gasket or apply silicone around the perimeter of the 

hole to prevent leakage.

• Insert unit into hole from the front side of the panel.
• Slide the mounting bracket securely against the panel from the rear of 

the unit.

• Wiring diagram is displayed on the top of the control.

Wiring

Avoid installing the temperature probe cables and the digital input wires
in close proximity of any power cables. If the length of the probe cables
is longer than 100 meters, a recalibration adjustment may be made
using the P1 parameter.

SPECIFICATIONS
Probe Range: 

PTC: -58 to 302°F (-50 to 150°C)
NTC: -58 to 230°F (-50 to 110°C).

Input:

PTC (1000Ω @ 25°C) / NTC (10KΩ @ 25°C).

Output: 

R1 SPDT Relay Resistive Load 16A, Inductive Load

10 FLA, 60 LRA @ 240 VAC.

Horsepower Rating: 

1HP @ 240 VAC.

Control Type:

On/Off.

Power Requirement: 

115 VAC, 230 VAC, 12 VAC/VDC, 24

VAC/DC (±10%) depending on model.

Power Consumption: 

3.6VA (115/230/24 V), 1.5VA (12V).

Accuracy: 

±1% FS.

Display: 

3 Digits Plus Sign.

Resolution:

0.1°.

Memory Backup: 

Non-Volatile Memory.

Ambient Temperature: 

32 to 131°F (0 to 55°C).

Weight: 

2.3 oz (65 g).

Front Protection:

IP65.

Agency Approvals: 

CE, UL.

3 [76.20]

1-3/8 

[35.08]

1-3/64 
[26.67]

2-3/4 [69.85]

2-5/8 [66.74]

2-7/16 [61.98]

T-TS3:TEMPLATE  10/7/09  1:39 PM  Page 1