Operating Modes 

 
The  KlassKeeper  heat  pump  has  several  modes  of  operation  including:  heating,  cooling  (first  stage), 
cooling (second stage), and fan. The unit is also equipped with an energy recovery ventilator (ERV). Each 
of  these  modes  of  operation  is  invoked  by  closing  the  associated  digital  input  on  the  internal  unit 
controller or via BAS, third party controller or thermostat. 
  

 

Heating 

In order to put the unit into heating mode, contact DI1 on the unit controller must be closed through a 
dry contact on the thermostat or the unit-mounted third party controller by others or BAS. This will first 
activate the main fan in low-speed, followed by high-speed if the heat call remains in place for 10 minutes 
or more. A modulating heat valve that controls the flow of hot water through the unit’s heating coil is 
opened 100% whenever a heat call is in place.  

 
Cooling 

In order to put the unit into cooling mode, contact DI2 on the unit controller must be closed through a 
dry contact on the thermostat or the unit-mounted third party controller by others. This will activate the 
fan in high speed, and will also start the first stage of the compressor for cooling. A cooling valve that 
directs water to the condenser will also be opened whenever there is a cool call in place. 
 
To bring on the second stage of cooling, contact DI3 on the unit controller must be closed through a dry 
contact  on  the  unit  mounted  third  party  controller  by  others.  In  order  for  second  stage  cooling  to 
commence, first stage cooling must first be activated.  
 
Note  that  each  compressor  stage  has  a  minimum  off-time  of  one  minute  between  calls.  There  is  no 
minimum on-time. 

 

 

During  cooling  operation, if  the  fresh  air  entering  temperature (FRSH-EAT)  is  cooler than  the  exhaust 
entering  air  temperature  (EX-EAT)  by  5°F  or  more,  the  heat  wheel  will  be  deactivated  to  allow  “free 
cooling” to take place.

 

 
Fan 

The  main fan  can  be  activated in  low  speed at  any  time  by  closing contact DI4  on  the  unit  controller 
through a dry contact on the unit mounted third party controller by others. If there is a heat or cool call 
in place, the operation of the fan is automatic.

 

 
Energy Recovery Ventilator (ERV) 

The KlassKeeper heat pump is equipped with an energy recovery ventilator that brings in fresh outside 
air, while simultaneously exhausting indoor air. A heat wheel is used to pre-condition the incoming fresh 
air, by recovering/rejecting heat from/to the outgoing exhaust air. 
 
To activate the ERV function, digital input DI5 on the unit controller must be closed through a dry-contact 
on the unit-mounted third party controller by others. This will activate both the ERV fan as well as the 
main fan (in low speed), while also energizing the heat wheel. The hot water valve modulates to maintain 
the discharge air temperature of 72

o

F (adjustable on the display or BAS) 

 

Содержание KlassKeeper KKV024

Страница 1: ...Last Revised April 2020 Installation Operation Maintenance Manual KlassKeeper Heat Pump KlassKeeper Models KKV024 KKV048...

Страница 2: ...rant Charge 5 Unit Clearances 5 INSTALLATION 6 Delivery and General Installation Checklist 6 Location 6 Cabinet Placement 6 Dry Walling when required 7 Piping 7 Wiring 8 OPERATION 9 Inputs Outputs 9 O...

Страница 3: ...st Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice MAINTENANCE 17 Inspect Filters 17 Check Fan motors annually 17 Visual Inspection 17 Amperage Che...

Страница 4: ...cting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interior use only and should be stored indoors at...

Страница 5: ...Keeper Installation Operation and Maintenance Manual 4 Copyright 2013 CGC Group Inc Last Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice Unit Dimen...

Страница 6: ...Charge oz 40 45 50 60 Consult factory Unit Clearances Clearances for the KlassKeeper units shall be provided such that the access panel swinging door opens and closes without obstruction to allow ser...

Страница 7: ...unit installation Specific site conditions may warrant variations in locations and dimensions 1 Remove packaging and inspect the unit Check for shipping damage or material shortage file a freight cla...

Страница 8: ...all screw must not be longer than the drywall thickness plus a maximum 3 8 Ensure drywall is not obstructing the swinging access door Piping CAUTION Piping must comply with all applicable codes and re...

Страница 9: ...bject to Change without Notice Wiring 1 Connect the wire harnesses between the chassis ERV and cabinet as per the below diagram 2 Connect the power plug to the receptacle in the cabinet Wire Harness T...

Страница 10: ...dry contacts on the third party controller or thermostat Analog Inputs TH1 Discharge Air Temperature TA TH2 Refrigerant Temperature TR TH3 Leaving Water Temperature TW TH4 Exhaust Entering Air Tempera...

Страница 11: ...will also be opened whenever there is a cool call in place To bring on the second stage of cooling contact DI3 on the unit controller must be closed through a dry contact on the unit mounted third pa...

Страница 12: ...ED Flashcode The Flex controller has a multi colored Alarm LED that is used to communicate the previous alarm if any through the use of flashcodes If there have been no alarms this LED will be green I...

Страница 13: ...ompressor has been running for three minutes a low pressure alarm will be activated the compressorwill be turned off the general alarm contact K7 will be energized a flashcode of 5 will be displayed a...

Страница 14: ...ovides information about the unit s operation The first button on the left allows the user to scroll through three separate screens Screen 1 This screen provides information on the alarm status of the...

Страница 15: ...m Central heat injection and rejection equipment is automatically controlled via a CGC control panel or equivalent to provide the required loop water temperature for correct KlassKeeper Bulldog Heat P...

Страница 16: ...speed the unit must be placed into cool mode Clean Unit Filters Check to ensure the unit filters are clean each KlassKeeper unit is equipped with three filters a pleated supply air filter and a wire f...

Страница 17: ...system problems may cause less than optimum operation In the event that the qualified commissioning agents suspect there is an operational problem with the heat pump they need to inform the factory im...

Страница 18: ...esh air filter unscrew the corresponding access panel on the left of the cabinet and slide the filter out Slide a new filter into place make certain the arrow on the filter is pointing in the directio...

Страница 19: ...t is reset or power is disconnected for 20 seconds NOTE If the heat pump must be reset more than twice check the unit for a dirty air filter abnormal entering water temperature inadequate water flow d...

Отзывы: