900 Series

Buccaneer

IP68 Sealed Electrical Cable Connectors

Wiring Assembly Instructions

www.bulgin.co.uk

Buccaneer 900 Series Environmentally Sealed Connectors

Mains Wire Connections 

Important connect wires 
Brown to terminal L 
Blue to terminal N
Green/Yellow to 
terminal E 

Specification

Electrical:

2, 3, 4 and 5 pole

7 pole

Current Rating:

32A, per contact

32A, per contact

Voltage Rating:

600V ac/dc, 50/60Hz

415V ac/dc

Contact Resistance:

<10m

(initial)

<10m

(initial)

Insulation Resistance:

>10

6

M

(@ 500V dc)

>10

6

M

(@ 500V dc)

Dielectric strength:

2.2kV ac min

2.2kV ac min

Approvals:

UL, VDE

UL (pending), VDE 

Material:

Body Mouldings:

Polyamide

Flammability Rating:

UL94V-0

Contacts:

Machined Solid Brass, Nickel plated

O Rings:

Nitrile

Panel Sealing Gasket:

Silicone Rubber

Mechanical:

Sealing:

IP68, EN60529

Contact Accommodation: 2.5 to 4mm

2

(13-10AWG) conductor, single or 

multi stranded

Cable Retention force: 22mm dia, 150N

15mm dia, 150N
7mm dia, 80N

Cable Acceptance and 
Gland Tightening Torques:

Cable dia

Gland Colour

Tightening Torque

PX0 version

13-15mm

Yellow (standard) 3.16Nm (28 lb/in)

11-13mm

Black

3.16Nm (28 lb/in)

9-11mm

White

3.16Nm (28 lb/in)

7-9mm

Dark Grey

3.16Nm (28 lb/in)

PXA version

20-22mm

Yellow (standard) 3.16Nm (28 lb/in)

18-20mm

Black

3.16Nm (28 lb/in)

16-18mm

White

3.16Nm (28 lb/in)

14-16mm

Dark Grey

3.16Nm (28 lb/in)

Panel mount nut

-

-

2.25Nm

Flange & Bulkhead
fixing screws

-

-

0.9Nm

IMPORTANT - PLEASE READ

Before using the connector, it is important that these instructions are
carefully read and understood to ensure the connector system is
completely water tight and electrically safe. 
IF IN DOUBT CONSULT A QUALIFIED ELECTRICIAN.

The 900 Series Buccaneer is available in 2, 3, 4, 5 and 7 pole versions.
The 3, 4, 5 and 7 pole versions have a ‘Leading Earth’ pin arrangement
for added protection.

The socket insert of the connector should always be the live part of the
connector from the supply. The pin insert of the connector should always
lead to the load or electrical device. The pin or socket inserts can be
fitted to any body style to provide the correct arrangement for the
application.

To ensure efficient sealing use only smooth, circular cable with
appropriate gland for the cable diameter. The sealing glands supplied
with the Flex and Flex In-line connectors accommodate cables sizes as
follows:

Version

Cable Dia.

Cable Gland Colour

PX0 13-15mm

Yellow 

(standard)

PX0

11-13mm

Black 

PX0

9-11mm

White 

PX0

7-9mm

Dark Grey

PXA 20-22mm

Yellow 

(standard)

PXA

18-20mm

Black 

PXA

16-18mm

White

PXA

14-16mm

Dark Grey 

Assembly/Wiring instructions

1.  Remove the pin or socket insert from the housing of the connector.

There is a slot for a flat blade screwdriver in the centre of the insert.
NOTE: The inserts have a LEFT HAND THREAD and should be turned

clockwise

to remove.

2.  For Flex and In-Line connector bodies, remove the gland nut, gland

cage and gland from the rear of the housing and slide onto the
cable. NOTE for PXA version there is no gland cage. Thread the
cable through the connector body. See assembly drawings, figs. 1-5
and 8 for different body styles.

3.  Prepare the cable and bare the wire ends as shown in fig. 6, wire

stripping details.

4.  Insert the bared wire ends into the terminals on the back of the

pin/socket insert and fully tighten the wire retention screws.
NOTE: If the connector is to be used with ‘mains’ voltages, ensure
the wires are connected in the correct orientation as shown in the
diagram below.
After the wires have been connected securely, pull the cable and
insert back into the housing and tighten with a screwdriver to ensure
the insert is seated correctly.
NOTE: LEFT HAND THREAD, turn the insert 

anti-clockwise

when

assembling.
When assembling the Chassis (fig 3) and Flange (fig 4 and 5)
housing types, the cable should be left free behind the panel to
prevent it twisting.

5.  For Flex and Flex In-line housings:

PX0 version: Slide the gland, gland cage and gland nut along the
cable into the body and tighten the gland nut to the appropriate
torque to seal.

Please note change to PXA assembly:

PXA version: Slide 1 washer, the gland, the final washer and gland
nut along the cable into the body and tighten to the appropriate
torque to seal then tighten clamp screws to secure. See fig 8.

6.

For the Bulkhead, Flange and Chassis body styles, correctly seat the
gaskets and housing onto the mounting surface and secure with rear
nut or screws/bolts with seals. Ensure all seals and glands are kept
clean during assembly.

NOTE: To ensure that the correct sealing properties of the connector are
achieved it is imperative that all ‘O’ rings are correctly located and
seated before assembly. Please refer to the exploded diagrams for the
locations of these seals. 

Part no.: 13672 Issue no: 8

IF IN DOUBT SEEK ADVICE

IMPORTANT SAFETY NOTICE

For your protection all mains (250V) equipment
used out of doors, in damp or wet conditions
should be supplied from a correctly fused
source and protected by an approved R.C.D. to
BS7071, BS7288, BS4293, BS EN 61008-1,
BS EN 1008-2-2