![Buhler TC-MIDI 6111 Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/buhler/tc-midi-6111/tc-midi-6111_installation-and-operation-instructions-manual_2827967042.webp)
TC-MIDI (+)
9.5 Performance data
TC-MIDI
Ambient temperature (°C)
Cooling capacity (kJ/h)
TC-MIDI 6111 (X2)
TC-MIDI 6112 (X2)
TV-SS
DTV
Note: The limit curves for the heat exchangers exchanger apply to a dew point of 50 °C.
TC-MIDI+
Ambient temperature (°C)
Cooling capacity (kJ/h)
TC-MIDI+ 6121 (X2)
TC-MIDI+ 6122 (X2)
STV-2 in series (55°C)
STV-2 in series (70°C)
Note: The capacity of STG-2 heat exchanges is equivalent to the maximum cooling capacity of the cooler.
9.6 Heat exchanger
9.6.1 Heat exchanger description
TC-MIDI
The energy content of the sample gas and the required cooling capacity of the gas cooler is determined by three parameters: gas
temperature
ϑ
G
, dew point
τ
e
(moisture content) and volume flow v. The outlet dew point rises with increasing energy content of
the gas. The approved energy load from the gas is therefore determined by the tolerated rise in the dew point.
The following limits are specified for a standard operating point of
τ
e
= 50 °C and
ϑ
G
= 70 °C. The maximum volume flow v
max
in
Nl/h of cooled air is indicated, so after moisture has condensed.
If the values fall below
τ
e
and
ϑ
G
, the flow v
max
may be increased. For example, on the TG heat exchanger the parameter triple
τ
e
= 40 °C,
ϑ
G
= 70 °C and v = 425 Nl/h may also be used in place of
τ
e
= 50 °C,
ϑ
G
= 70 °C and v = 345 Nl/h.
Please contact our experts for clarification or refer to our design program.