Nivotemp NT M-XP
Temperature
Used to configure at which temperature to output the maximum analogue signal. This is configured in menu:
Measured variable
____
An_
Measured variable main menu
Analog OutX
A I.Hi
Analog MaxX
Maximum value assignment
____
Selection menu
[ o.Lo - o.Hi ]
Settings menu Analog X
Setting range:
0 °C to 100 °C
(32 °F to 212 °F)
Note:
– The output range setting must not be less than 10 % of the measuring range:
A I.Hi
–
A I.Lo
>=
10%
– If the range is set too low, the analogue value output may have grades.
5.8.2 Analogue output x: Lower limit assignment
Liquid Level
Used to configure at which liquid level to output the minimum analogue signal. This is configured in menu:
Measured variable
____
An_
Measured variable main menu
Analog OutX
A I.Lo
Analog MinX
Minimum value assignment
____
Selection menu
[ o.Lo - o.Hi ]
Settings menu Analog X
Setting range:
[
o.Lo
] … [
o.Hi
]
Note:
– The output range setting must not be less than 10 % of the measuring range:
A I.Hi
–
A I.Lo
>=
10% * (
o.Hi
–
o.Lo
)
– If the range is set too low, the analogue value output may have grades.
Temperature
Used to configure at which temperature to output the minimum analogue signal. This is configured in menu:
Measured variable
____
An_
Measured variable main menu
Analog OutX
A I.Lo
Analog MinX
Minimum value assignment
____
Selection menu
[ o.Lo - o.Hi ]
Settings menu Analog X
Setting range:
0 °C to 100 °C
(32 °F to 212 °F)
Note:
– The output range setting must not be less than 10 % of the measuring range:
A I.Hi
–
A I.Lo
>=
10%
– If the range is set too low, the analogue value output may have grades.
5.8.3 Analogue output x: Signal type assignment
The analogue output can be defined as a voltage or current output with different value ranges. This is configured in menu:
Measured variable
____
An_
Measured variable main menu
Analog OutX
A.ou_
Set A.OUtX
Output function
_ _
Selection menu
i I - u 3
Settings menu Analog X
The options are:
4 mA to 20 mA
2 V to 10 V
0 V to 10 V
0 V to 5 V
23
Bühler Technologies GmbH
BE100023 ◦ 06/2021