Operating the heating system

6

Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!

20

6.1.3 Settings menu

Three settings can be made in the Settings menu:

– Target boiler output;
– Target pump run-over time;
– DHW mode target status.

If you will be absent for a long period while there is a risk 
of freezing, the target pump run-over time will have to be 
set (

 section 7.4. on page 23).

The target boiler output and the DHW mode 
target status should be set by a registered 
installer.

Settings menu

Step 1

[\/2/4| 

Display value. Currently measured CH (boiler) flow temperature in °C.

Also see section 8.1, page 24.

Step 2

Open the “Adjustments” menu?

Yes:

 step 

3

No:

 step 

1

Step 3

To open the "Settings" menu: Press and hold the 

d

e

 buttons for more than 2 seconds.

Step 4

[l/?/?|

 Display setting. As soon as the display shows 

[l/?/?|

, the "Settings" menu is open. 

You can set the boiler output using the first parameter shown on the display (also see 
section 8.2, page 24).

Step 5

Adjust boiler output?

Yes:

 step 

6

No:

 step 

7

Step 6

Lower:

Decrease the target boiler output with the 

c

 button. The minimum setting is

[l/2/5|

 = 25 % with an 80-kW boiler and 

[l/2/0|

 = 20 % with a 65 and 100-kW boiler.

Higher:

 Increase the target boiler output with the 

d

 button. The maximum setting is

[l/?/?|

 = 100 %. This is equal to the factory setting.

Step 7

Press the 

e

 button.

Step 8

[f/\/5|

 Display setting. Set the second parameter as soon as the display shows 

[f/\/5|

This parameter shows the target pump run-over time in minutes after heating operation has 
ended (also see section 8.2, page 24).

Note

: Do not set a pump run-over time of less than 

[f/\/5|

 (= 5 minutes).

Step 9

Set the pump run-over time after heating operation has ended?

Yes:

 step 

10

No:

 step 

11

Step 10

Lower:

Decrease the target pump run-over time after the end of heating operation with the 

c

button. The minimum setting is 

[f/\/0|

 = 0 minutes. The factory default setting is 5 minutes. 

CAUTION

 Do not set the target pump run-over time after the end of heating operation to less 

than 5 minutes.

Higher:

 Increase the target pump run-over time after the end of heating operation with the 

d

button. The maximum setting is 

[f/1/d|

 = 24 hours.

Step 11

Press the 

e

 button.

Step 12

[c/\/1|

 Display setting. Set the third parameter as soon as the display shows 

[c/\/1|

This parameter indicates the DHW mode status setting. This enables DHW mode to be 
switched off or on. This setting has priority over other DHW mode settings, such as on the 
room thermostat. Also see section 8.2, page 24.

Step 13

Set the DHW mode status?

Yes:

 step 

14

No:

 step 

15

table 7 Settings

Содержание Logamax plus GB162-100 kW

Страница 1: ...User Manual Condensing gas boiler Logamax plus GB162 65 80 100 7217 5100 03 2010 GB For the end user Please read thoroughly before operating the boiler...

Страница 2: ...Checking and correcting the system pressure 12 5 1 1 Filling the heating system 13 5 2 1 Setting the CH boiler flow temperature 15 5 2 2 Setting the DHW temperature 16 5 2 4 Setting the room controll...

Страница 3: ...and directives for all rated input installation BS 1212 BS 4814 1990 Specification for expansion vessels using an inter nal diaphragm for sealed hot water heating sys tems BS 5482 Code of practice for...

Страница 4: ...n for Installation of gas fired hot water boilers of rated inputs between 70 kW net and 1 8 MW net 2nd and 3rd family gases BS EN 15417 2006 Gas fired central heating boilers Specific require ments fo...

Страница 5: ...c controller 1 2 3 4 5 6 7 11 10 9 8 Item Description 1 Mains switch Heating On Off 2 Reset button fault reset button 3 Chimney sweep button for manual operation 4 Service button 5 Service Connector f...

Страница 6: ...ments 6 2 Permanent clearances The boiler must be located in an area with the following permanent clearances 50 mm 30 mm 250 mm with pump group 0 mm 0 mm The installer or service engineer must be able...

Страница 7: ...ult in the malfunctioning of the boiler and damage to the heat exchanger DO NOT treat the water with products such as pH adjusting substances chemical additives and anti freeze or water softeners 3 6...

Страница 8: ...Universal Burner Automat 3 DAMAGE TO THE INSTALLATION due to insufficient or improper cleaning and maintenance Have the heating system inspected cleaned and serviced by a registered Gas Safe installe...

Страница 9: ...g 3 item 1 The BC10 basic controller consists of the following components Mains switch The mains switch fig 4 item 1 is used to switch the boiler on and off Reset button If a fault has occurred you ma...

Страница 10: ...agnostic purposes when servicing Burner On Off LED The Burner On Off LED fig 5 item 6 lights up when the burner of the boiler is switched on and it is extin guished when the burner is switched off The...

Страница 11: ...isplay will flash if a locking fault is detected DHW temperature dial The DHW temperature dial fig 6 item 11 is used to select the required temperature of the hot water in the hot water cylinder The u...

Страница 12: ...checked every day for 1 week The maximum pressure in the heating system meas ured directly at the boiler must not exceed 2 5 bar Switch on the mains switch fig 7 item 1 on the BC10 position 1 Press th...

Страница 13: ...ms fig 10 Control valve stop valve including a double check valve on the mains cold water supply pipe Temporary connection to be removed after filling fill ing loop Control valve stop valve on the hea...

Страница 14: ...pprox one week and the pressure reading on the display is less than 1 0 bar the system has to be topped up The pressure loss in a heating system is caused by air bubbles escaping via fittings and auto...

Страница 15: ...ion 1 5 2 1 Setting the CH boiler flow temperature Set the dial for the maximum CH boiler flow temperature fig 16 item 2 to set the required temperature according to table 3 fig 15 Opening the gas val...

Страница 16: ...em is not used for a long period e g during a holiday and a temperature of less than 60 C has been set it is advisable to flush the hot water cylinder before using it again Flushing means fully openin...

Страница 17: ...nd switches it off at a CH boiler flow temperature of 15 C The heating system is not protected against frost 5 2 4 Setting the room controller Make the settings on the room controller e g RC35 fig 18...

Страница 18: ...temperature permanent indi cation the working pressure and the operating codes are shown Proceed as follows fig 19 BC10 basic controller 1 2 3 4 Normal operation menu Step 1 2 4 Display value Current...

Страница 19: ...of the BC10 basic controller control panel now applies The Heat request LED lights up DHW mode is possible during manual operation Step 5 Press the e button Step 6 p 1 6 Display value Currently measur...

Страница 20: ...kW boiler Higher Increase the target boiler output with the d button The maximum setting is l 100 This is equal to the factory setting Step 7 Press the e button Step 8 f 5 Display setting Set the sec...

Страница 21: ...c 1 means On c 0 means Off Please note Setting c 0 switches off the hot water cylinder frost protection Step 15 Have at least 5 seconds passed without a button being pressed and or has the mains volta...

Страница 22: ...tic BC10 basic controller is provided in chapter 6 Operat ing the heating system page 18 Push on the control panel to open it fig 20 Switch off the heating system by pressing the mains switch of the B...

Страница 23: ...in cock or the radiator fig 23 The automatic air vent at the highest point of the heating system radiator see fig 14 page 14 must be open then 7 4 Long term absence while there is a risk of freezing I...

Страница 24: ...1 6 Current system pressure bar p 0 0 p 4 0 Display settings Display setting Meaning of display setting Unit Range Factory adjusted setting l 9 9 Configured target load 100 kW l 2 0 l 9 9 l 100 l l 9...

Страница 25: ...1 Operating phase The boiler cannot start up temporarily after a DHW request has ended e 0 c e 2 8 3 1 Pre operative phase The boiler prepares for a burner start up whenever a heat demand or a DHW req...

Страница 26: ...ing engineer e h 7 e Operating phase The system pressure is too low less than 1 0 bar p Operating phase The system pressure is too high over 4 0 bar or the pressure sensor has not detected a system pr...

Страница 27: ...Notes Logamax plus GB162 65 80 100 Subject to modifications resulting from technical improvements 27...

Страница 28: ...Orchard Dublin 10 Tel 01 6305700 Fax 01 6305706 01 6305715 www cfquadrant ie e mail sales cfquadrant ie 721 751A 0004 Buderus Cotswold Way Warndon Worcester WR4 9SW Customer service 0844 892 9700 Tech...

Отзывы: